SPECIFICATIONS
144
Ceiling concealed type
Fresh air intake type
Power source
Cooling capacity
(Nominal)
*2 Power input
*2 Current input (220 V)
Temp. range of cooling
Heating capacity
(Nominal)
*2 Power input
*2 Current input (220 V)
Temp. range of heating
External finish
External dimension HxWxD
Net weight
Heat exchanger
FAN
Type x Quantity
*4, 5 External
static press.
Motor Type
Motor output
Driving mechanism
*4, 5 Air flow rate
(Low-Mid-High)
Sound pressure level (measured in anechoic room) Normal-airflow rate mode <High-airflow rate mode> Normal-airflow rate mode <High-airflow rate mode> Normal-airflow rate mode <High-airflow rate mode>
(Low-Mid-High)
Air filter
Refrigerant piping
Liquid (R410A) mm (in.)
diameter
Gas (R410A)
Field drain pipe size
Optional parts
Drain pump kit
Long life filter
Filter box
Notes:
*1 Cooling capacity indicates the maximum value at operation under the following condition. Cooling: Indoor 33°CDB/28°CWB, Outdoor 33°CDB. The set temperature of the
remote controller is 18°C.
*2 The value are measured at the factory setting of airflow mode and external static pressure.
*3 Heating capacity indicates the maximum value at operation under the following condition. Heating: Indoor 0°CDB/-2.9°CWB, Outdoor 0°CDB/-2.9°CWB. The set
temperature of the remote controller is 25°C.
*4 The factory setting of airflow mode and external static pressure mode is shown without < >. Refer to "Fan characteristics curves", according to the external static pressure,
in DATA BOOK for the usable range of air flow rate.
*5 If the airflow rate is over the usable range, dew drop can be caused from the air outlet and the air flow rate is changed automatically because of the output down by the
fan motor control. If the air flow rate is less than the usable range, condensation from the unit surface can be caused.
*6 Regarding P250VMHS-E-F, the middle notch air flow rate is different from the spec value when the external static pressure setting is set to 100Pa. See "Fan characterics
curves" in DATA BOOK for the details.
The combination of fresh air intake type indoor units with other types of indoor units to handle internal thermal load which may cause the conflict of operation mode. It is not
recommended when fresh air intake type indoor unit is connected to the Y or WY series.
Depending on the air conditioning load, outside temperature, and due to the activation of protection functions, the desired preset temperature may not always be achieved
and the outlet air temperature may swing. Note that untreated outside air may be delivered directly into the room upon the activation of protection functions.
Fresh air intake type indoor units cannot be connected to an outdoor unit together with PWFY series.
The maximum connectable indoor units to 1 outdoor unit are 110% (100% in case of heating below -5°C).
When fresh air intake type indoor units connect to an outdoor unit together with other types of indoor unit, the total capacity of fresh air intake type indoor units needs to be
30% or less of the connected outdoor unit capacity.
The AUTO mode on the local remote controller is available only when fresh air intake type indoor unit is connected to the R2 or WR2 series of outdoor unit.
The system changeover function is available only when all the connected indoor units are fresh air intake type indoor units.
The fan temporary stops during defrost.
The cooling and heating capacities are the maximum capacities that were obtained by operating in the above air conditions and with a refrigerant pipe of about 7.5 m and a
level difference of 0 m.
The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical information in DATA BOOK for the details.
Thermo off (Fan) operation automatically starts either when temperature is lower than 17°CDB in cooling mode or when the temperature exceeds 20°CDB in heating mode.
Dry mode is not available.
When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
Un-conditioned outdoor air such as humid air or cold air blows to the indoor during thermo off operation, which may occur dew condensation on the grills and ducts. Please
insulate the grills, ducts, and rooms to prevent dew condensation properly.
Air filter must be installed in the air intake side. The filter should be attached where easy maintenance is possible in case of usage of field supply filters.
PEFY-P VMHS-E-F
PEFY-P125VMHS-E-F
1-phase 220-230-240 V 50/60 Hz
*1
kW
14.0
*1 BTU/h
47,800
kW
0.220
A
1.43
17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is lower
than 17°CD.B.
*3
kW
8.9
*3 BTU/h
30,400
kW
0.230
A
1.52
-10°CD.B. ~ 20°CD.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is
higher than 20°CD.B.
Galvanized
mm
380 x 1,195 x 900
in.
15 x 47-1/16 x 35-7/16
kg (lbs)
49 (109)
Cross fin (Aluminum fin and copper tube)
Sirocco fan x 1
Pa
<100> - <150> - 200 - <250>
mmH
O
<10.2> - <15.3> - 20.4 - <25.5>
2
DC motor
kW
0.244
Direct-driven by motor
Normal-airflow rate
<High-airflow rate
mode
mode>
m
3
/min
14.0 - 15.5 - 18.0
15.5 - 18.0 - 20.0
L/s
233 - 258 - 300
258 - 300 - 333
cfm
494 - 547 - 636
547 - 636 - 706
*2 dB <A>
34-37-41
36-40-42
Option: Synthetic fiber unwoven cloth filter
(long life filter).
9.52 (3/8) Brazed
mm (in.)
15.88 (5/8) Brazed
mm (in.)
O.D.32 (1-1/4)
PAC-DRP10DP-E2
PAC-KE89LAF
PAC-KE140TB-F
PEFY-P200VMHS-E-F
1-phase 220-230-240 V 50/60 Hz
22.4
76,400
0.260
1.66
17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is lower
than 17°CD.B.
13.9
47,400
0.270
1.85
-10°CD.B. ~ 20°CD.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is
higher than 20°CD.B.
Galvanized
470 x 1,250 x 1,120
18-9/16 x 49-1/4 x 44-1/8
78 (172)
Cross fin (Aluminum fin and copper tube)
Sirocco fan x 2
<100> - <150> - 200 - <250>
<10.2> - <15.3> - 20.4 - <25.5>
DC motor
0.375
Direct-driven by motor
Normal-airflow rate
<High-airflow rate
mode
mode>
22.5 - 25.0 - 28.0
25.0 - 28.0 - 32.0
375 - 417 - 467
417 - 467 - 533
794 - 883 - 989
883 - 989 - 1,130
35-38-41
36-39-42
Option: Synthetic fiber unwoven cloth filter
(long life filter).
9.52 (3/8) Brazed
19.05 (3/4) Brazed
O.D.32 (1-1/4)
PAC-KE06DM-F
PAC-KE85LAF
PAC-KE250TB-F
PEFY-P250VMHS-E-F *6
1-phase 220-230-240 V 50/60 Hz
28.0
95,500
0.350
2.16
17°CD.B./15.5°CW.B. ~ 43°CD.B./35°CW.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is lower
than 17°CD.B.
17.4
59,400
0.360
2.38
-10°CD.B. ~ 20°CD.B.
* Thermo-off (FAN-mode) automatically
starts if the outdoor temperature is
higher than 20°CD.B.
Galvanized
470 x 1,250 x 1,120
18-9/16 x 49-1/4 x 44-1/8
81 (179)
Cross fin (Aluminum fin and copper tube)
Sirocco fan x 2
<100> - <150> - 200 - <250>
<10.2> - <15.3> - 20.4 - <25.5>
DC motor
0.375
Direct-driven by motor
Normal-airflow rate
<High-airflow rate
mode
mode>
28.0 - 31.0 - 35.0
31.0 - 35.0 - 40.0
467 - 517 - 583
517 - 583 - 667
989 - 1,095 - 1,236 1,095 - 1,236 - 1,412
38-40-44
38-41-45
Option: Synthetic fiber unwoven cloth filter
(long life filter).
9.52 (3/8) Brazed
22.22 (7/8) Brazed
O.D.32 (1-1/4)
PAC-KE06DM-F
PAC-KE85LAF
PAC-KE250TB-F