SPECIFICATIONS
82
WR2-Series
PQRY-P YLM-A1
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
EER
Temp. range of
Indoor
cooling
Inlet water
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor
heating
Inlet water
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level
(measured in anechoic room)
Sound power level
(measured in anechoic room)
Refrigerant piping High pressure
diameter
Low pressure
Circulating water Water flow rate
Pressure drop
Operating
volume range
Compressor
Type
Starting method
Motor output
Case heater
External finish
External dimension HxWxD
Protection
High pressure protection
devices
Inverter circuit (COMP.)
Compressor
Refrigerant
Type x original charge
Net weight
Heat exchanger
Water volume in
plate
Water pressure
Max.
Optional parts
Notes:
*1,*2 Nominal conditions
Cooling
Heating
*The ambient temperature of the heat source unit needs to be kept below 40ºCD.B.
*The ambient relative humidity of the heat source unit needs to be kept below 80%.
*The heat source unit should not be installed at outdoor.
*Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
*Be sure to provide interlocking for the unit operation and water circuit.
*Nominal condition *1,*2 are subject to JIS B8615-2.
*Due to continuing improvement, above specification may be subject to change without notice.
PQRY-P200YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
*1
kW
22.4
kcal / h
20,000
*1 BTU / h
76,400
kW
3.71
A
6.2-5.9-5.7
kW / kW
6.03
W.B.
15.0~24.0°C (59~75°F)
°C
10.0~45.0°C (50~113°F)
*2
kW
25.0
kcal / h
21,500
*2 BTU / h
85,300
kW
3.97
A
6.7-6.3-6.1
kW / kW
6.29
D.B.
15.0~27.0°C (59~81°F)
°C
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~20
dB <A>
46
dB <A>
60
mm (in.)
15.88 (5/8) Brazed
mm (in.)
19.05 (3/4) Brazed
m
3
/ h
5.76
L/min
96
cfm
3.4
kPa
24
3
m
/ h
3.0 ~ 7.2
Inverter scroll hermetic compressor
Inverter
kW
4.8
kW
Galvanized steel sheets
mm
1,100 x 880 x 550
in.
43-5/16 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Over-heat protection
R410A x 5.0 kg (12 lbs)
kg (lbs)
173 (382)
plate type
L
5.0
MPa
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Indoor
Inlet water temperature
27ºCD.B./19ºCW.B.
30ºC (86ºF)
(81ºFD.B./66ºFW.B.)
20ºCD.B. (68ºFD.B.)
20ºC (68ºF)
PQRY-P250YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
28.0
25,000
95,500
4.90
8.2-7.8-7.5
5.71
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
31.5
27,100
107,500
5.08
8.5-8.1-7.8
6.20
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~25
48
62
19.05 (3/4) Brazed
22.2 (7/8) Brazed
5.76
96
3.4
24
3.0 ~ 7.2
Inverter scroll hermetic compressor
Inverter
6.2
Galvanized steel sheets
1,100 x 880 x 550
43-5/16 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection
R410A x 5.0 kg (12 lbs)
173 (382)
plate type
5.0
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Pipe length
Level difference
7.5m (24-9/16ft.)
0m (0ft.)
PQRY-P300YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
33.5
30,000
114,300
6.04
10.1-9.6-9.3
5.54
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
37.5
32,300
128,000
6.25
10.5-10.0-9.6
6.00
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~30
54
68
19.05 (3/4) Brazed
22.2 (7/8) Brazed
5.76
96
3.4
24
3.0 ~ 7.2
Inverter scroll hermetic compressor
Inverter
7.7
Galvanized steel sheets
1,100 x 880 x 550
43-5/16 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection
R410A x 5.0 kg (12 lbs)
173 (382)
plate type
5.0
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1

Advertisement