Download Print this page

Mitsubishi Electric Y Series Manual page 158

Hide thumbs Also See for Y Series:

Advertisement

SPECIFICATIONS
158
Floor standing type
Exposed type
Power source
Cooling capacity
*1
*1 BTU/h
Heating capacity
*1
*1 BTU/h
Power
Cooling
consumption
Heating
Current
Cooling
Heating
External fi nish(Munsell No.)
Dimension H x W x D
Net weight
Heat exchanger
FAN
Type x Quantity
Airfl ow rate
*2 m
(Lo-Hi)
External static pressure
Motor
Type
Output
Air fi lter
Refrigerant
Gas
pipe diameter
(Flare)
Liquid
(Flare)
Field drain pipe diameter
Sound pressure level
(Lo-Hi)
*2 *3 *4
Notes:
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27°C(81°F)DB/19°C(66°F)WB,Outdoor 35°C(95°F)DB
Heating Indoor : 20°C(68°F)DB, Outdoor 7°C(45°F)DB/6°C(43°F)WB
*2 Air fl ow rate/Sound pressure level are in (Low-High)
PFFY-P VLEM-E
PFFY-P20VLEM-E PFFY-P25VLEM-E PFFY-P32VLEM-E PFFY-P40VLEM-E PFFY-P50VLEM-E PFFY-P63VLEM-E
kW
2.2
7,500
9,600
kW
2.5
8,500
10,900
kW
0.04 / 0.06
kW
0.04 / 0.06
A
0.19 / 0.25
A
0.19 / 0.25
mm
630 x 1,050 x 220
in.
24-13/16 x 41-3/8 x 8-11/16
kg(lbs.)
28 (62)
Sirocco fan x 1
3
/min
5.5-6.5
L/s
92-108
cfm
194-230
Pa
kW
0.015
mm(in.)
mm(in.)
mm(in.)
dB<A>
34-40
1-phase 220-240V 50Hz / 1-phase 208-230V 60Hz
2.8
3.6
12,300
3.2
4.0
13,600
0.06 / 0.07
0.06 / 0.07
0.29 / 0.30
0.29 / 0.30
Acrylic paint (5Y 8/1)
630 x 1,170 x 220
24-13/16 x 46-1/8 x 8-11/16
30 (67)
Cross fi n (Aluminum plate fi n and copper tube)
7.0-9.0
117-150
247-318
0
1-phase induction motor
0.018
PP Honeycomb fabric (washable)
ø12.7 (ø1/2)
ø6.35 (ø1/4)
I.D.26 (1) <Accessory hose O.D.27 (1-3/32) (top end :20 (13/16))>
35-40
4.5
5.6
15,400
19,100
5.0
6.3
17,100
21,500
0.065 / 0.075
0.085 / 0.09
0.065 / 0.075
0.085 / 0.09
0.32 / 0.33
0.40 / 0.41
0.32 / 0.33
0.40 / 0.41
630 x 1,410 x 220
24-13/16 x 55-9/16 x 8-11/16
32 (71)
36 (80)
Sirocco fan x 2
9.0-11.0
12.0-14.0
150-183
200-233
318-388
424-494
0.030
0.035
38-43
*3 Measured point : 1m x 1m, Power supply : AC240V/50Hz
· 1dB<A> lower at AC230V/50Hz
· 2dB<A> lower at AC220V/50Hz
· 3dB<A> lower at 1.5m x 1.5m point
*4 It is measured in anechoic room.
7.1
24,200
8.0
27,300
0.1 / 0.11
0.1 / 0.11
0.46 / 0.47
0.46 / 0.47
37 (82)
12.0-15.5
200-258
424-547
0.050
ø15.88 (ø5/8)
ø9.52 (ø3/8)
40-46