Wall-mounted type
Power source
Cooling capacity
*1
kW
*1 BTU/h
Heating capacity
*1
kW
*1 BTU/h
Power
Cooling*4
kW
consumption
Heating
kW
Current
Cooling*4
A
Heating
A
External finish(Munsell No.)
Dimension H x W x D
mm(in.)
Net weight
kg(lbs.)
Heat exchanger
FAN
Type x Quantity
3
Airflow rate
*2 m
/min
(Lo-Hi)
L/s
cfm
External static pressure
Pa
Motor
Type
Output
kW
Air filter
Refrigerant
Gas
mm(in.)
pipe diameter
(Flare)
Liquid
mm(in.)
(Flare)
Field drain pipe diameter
mm(in.)
Sound pressure level
dB<A>
(Lo-Hi)
*2 *3
Notes:
*1 Cooling/heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27°C(81°F)DB/19°C(66°F)WB, Outdoor : 35°C(95°F)DB
Heating Indoor : 20°C(68°F)DB, Outdoor : 7°C(45°F)DB/6°C(43°F)WB
*2 Airflow rate/Sound pressure level are in (low-high).
*3 It is measured in anechoic room.
*4 Electrical characteristic of cooling are included optional drain-pump.
Optional parts
Description
External LEV Box
Drain pump kit
PKFY-P VKM-E
PKFY-P63VKM-E
1-phase 220-230-240V 50Hz / 1-phase 220V 60Hz
7.1
24,200
8.0
27,300
0.05
0.04
0.37
0.30
Plastic (1.0Y 9.2/0.2)
365 x 1,170 x 295 (14-3/8 x 46-1/16 x 11-5/8)
Cross fin (Aluminum fin and copper tube)
Line flow fan x 1
16-20
267-333
565-706
DC motor
PP Honeycomb
ø15.88 (ø5/8)
ø9.52 (ø3/8)
I.D. 16(5/8)
39-45
Model
PAC-SK17LE-E
PAC-SG95LE-E
PAC-SK01DM-E
PAC-SH94DM-E
PKFY-P100VKM-E
11.2
38,200
12.5
42,600
0.08
0.07
0.58
0.51
21 (46)
20-26
333-433
706-918
0
0.056
ø15.88 (ø5/8) / ø19.05 (ø3/4)
(Compatible)
41-49
Applicable capacity
P10
P15, 20, 25, 32, 40, 50, 63
P10, 15, 20, 25, 32, 40, 50
P63, 100
SPECIFICATIONS