SPECIFICATIONS
224

Remote Controller

PAR-W21MAA
Item
ON / OFF
Operation mode switching
Water temperature setting
Preset temperature range limit
Water temperature display
Permit / Prohibit local operation
Schedule operation
Error display
Self check (Error history)
Test run
Circulating water replacement warning
Operation locking function
Centralized Controller
AE-200E
AE-50E
EW-50E
Item
Controllable unit
ON / OFF
Operation mode switching
Water temperature setting
Water temperature display
Permit / Prohibit local operation
Schedule operation
Error display
Test run
External input / output
Note:
Operation and displayed content vary depending on the indoor unit model.
EW-50E can be operated and monitored only from the Integrated Centralized Control Web.
However, when EW-50E is used as an expansion controller of AE-200E, EW-50E can be operated and monitored via AE-200E.
ON and OFF the operation of a group of units
Switches between Hot Water / Heating / Heating ECO / Anti - freeze / Cooling
* Available operation modes vary depending on the unit to be connected.
* Switching limit setting can be made via a remote controller.
Temperature can be set within the ranges below. (in increments of 1°C or 1°F)
Heating
30°C ~ 50°C (87°F ~ 122°F)
Heating ECO
30°C ~ 45°C (87°F ~ 113°F)
Hot Water
30°C ~ 70°C (87°F ~ 158°F)
Anti-freeze
10°C ~ 45°C (50°F ~ 113°F)
Cooling
10°C ~ 30°C (50°F ~ 87°F)
• The settable range varies depending on the unit to be connected.
Preset temperature range setting can be limited via a remote controller.
10°C ~ 90°C (50°F ~ 194°F)
(in increments of 1°C or 1°F)
• The settable range varies depending on the unit to be connected.
Individually prohibits operations of each local remote control function : ON / OFF,
Operation modes, water temperature setting, Circulating water replacement warning reset.
* Upper level controller may not be connected depending on the unit to be connected.
ON / OFF / Water temperature setting can be done up to 6 times one day in the week.
(in increments of a minute)
When an error is currently occurring on a unit, the afflicted unit and the error code are displayed.
Searches the latest error history by pressing the CHECK button twice.
Enables the Test run mode by pressing the TEST button twice.
* Test run mode is not available depending on the unit to be connected.
Displays the circulating water replacement warning via the unit message.
Clears the display by pressing the CIR.WATER button twice.
* Circulating water replacement warning is not available depending on the unit to be connected.
Remote controller operation can be locked or unlocked.
• All-switch locking
• Locking except ON / OFF switch
: Each unit
Up to 50 units / 50 groups "Up to 200 units / 200 groups via expansion controllers"
ON and OFF the operation of a group of units
Switches between Hot Water / Heating / Heating ECO / Anti - freeze / Cooling
* Available operation modes vary depending on the unit to be connected.
* Switching limit setting can be made via a remote controller.
Temperature can be set within the ranges below. (in increments of 1°C or 1°F)
[Booster unit]*
Heating
30°C ~ 50°C (87°F ~ 122°F)
Heating ECO** Invalid
Hot Water
30°C ~ 70°C (87°F ~ 158°F)
Anti-freeze
10°C ~ 45°C (50°F ~ 113°F)
Cooling
Invalid
• The settable range varies depending on the unit to be connected.
* "Air To Water" on the AE-200E screen indicates Booster unit group and Water HEX unit group.
** The temperature is controlled automatically in the Heating ECO. The user cannot change the
temperature settings.
10°C ~ 90°C (50°F ~ 194°F) (in increments of 1°C or 1°F)
• The settable range varies depending on the unit to be connected.
Individually prohibit operation of each local remote control function
(ON / OFF, Change operation mode, Set temperature).
Group is the smallest unit to which a weekly schedule can be assigned. The same schedule
can be applied collectively, or to each group, groups in a block, or groups on a floor.
• Up to 24 events can be scheduled for each day.
• "ON/OFF", "Operation mode", "Temperature Setting", and "Permit / Prohibit local operation"
can be scheduled.
• Five types of weekly schedule patterns (summer and winter) are available.
• Five operation patterns (A-E) can be set for each year, up to 50 days can be allocated to
each pattern.
When an error is currently occurring on an unit, the afflicted unit and the error code are displayed.
This operates air conditioner units in test run mode.
By using optional external input / output adaptor (PAC-YG10HA) you can set and monitor the following.
Input : By level signal : "Batch ON / OFF", "Batch emergency stop"
By pulse signal : "Batch ON / OFF", "Enable / disable local remote controller"
Output : "ON / OFF", "Error / Normal"
Description
: Each group
: Each block
: Each floor
Description
[Water HEX unit]*
Heating
30°C ~ 45°C (87°F ~ 113°F)
Heating ECO** Invalid
Hot Wate
Invalid
Anti-freeze
10°C ~ 45°C (50°F ~ 113°F)
Cooling
10°C ~ 30°C (50°F ~ 87°F)
: Each group
: Not available
Operations
Display
: Collective
: Not available
Operations
Display

Advertisement

loading

This manual is also suitable for:

S seriesWy seriesR2 seriesWr2 series