Download Print this page

Mitsubishi Electric Y Series Manual page 89

Hide thumbs Also See for Y Series:

Advertisement

WR2-Series
PQRY-P YSLM-A1
Model
Power source
Cooling capacity
*1
kW
(Nominal)
kcal / h
*1 BTU / h
Power input
kW
Current input
A
EER
kW / kW
Temp. range of
Indoor
W.B.
cooling
Inlet water
°C
Heating capacity
*2
kW
(Nominal)
kcal / h
*2 BTU / h
Power input
kW
Current input
A
COP
kW / kW
Temp. range of
Indoor
D.B.
heating
Inlet water
°C
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level
dB <A>
(measured in anechoic room)
Sound power level
dB <A>
(measured in anechoic room)
Refrigerant piping High pressure
mm (in.)
diameter
Low pressure
mm (in.)
Set Model
Circulating water Water fl ow rate
m
3
/ h
L/min
cfm
Pressure drop
kPa
Operating
m
3
/ h
volume range
Compressor
Type
Starting method
Motor output
kW
Case heater
kW
External fi nish
External dimension HxWxD
mm
in.
Protection
High pressure protection
devices
Inverter circuit (COMP.)
Compressor
Refrigerant
Type x original charge
Net weight
kg (lbs)
Heat exchanger
Water volume in
L
plate
Water pressure
MPa
Max.
Optional parts
Notes:
*1,*2 Nominal conditions
Indoor
27ºCD.B./19ºCW.B.
Cooling
(81ºFD.B./66ºFW.B.)
Heating
20ºCD.B. (68ºFD.B.)
*The ambient temperature of the heat source unit needs to be kept below 40ºCD.B.
*The ambient relative humidity of the heat source unit needs to be kept below 80%.
*The heat source unit should not be installed at outdoor.
*Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
*Be sure to provide interlocking for the unit operation and water circuit.
*Nominal condition *1,*2 are subject to JIS B8615-2.
*Due to continuing improvement, above specifi cation may be subject to change without notice.
PQRY-P450YLM-A1
7.20 + 7.20
120 + 120
4.2 + 4.2
44
4.5 + 4.5 ~ 11.6 + 11.6
Inverter scroll hermetic compressor
Inverter
11.6
Galvanized steel sheets
1,450 x 880 x 550
57-1/8 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch at 4.15 MPa (601 psi) High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
Over-heat protection
R410A x 6.0 kg (14 lbs)
217 (479)
plate type
5.0
2.0
Heat Source Twinning kit: CMY-Q200CBK
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Inlet water temperature
30ºC (86ºF)
7.5m (24-9/16ft.)
20ºC (68ºF)
PQRY-P900YSLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
101.0
86,900
344,600
19.38
32.7-31.0-29.9
5.21
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
113.0
97,200
385,600
19.74
33.3-31.6-30.5
5.72
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/2~50
57
73
28.58 (1-1/8) Brazed
41.28 (1-5/8) Brazed
Inverter scroll hermetic compressor
57-1/8 x 34-11/16 x 21-11/16
Over-heat protection, Over-current protection
Heat Source Twinning kit: CMY-Q200CBK
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Pipe length
Level diff erence
0m (0ft.)
SPECIFICATIONS
PQRY-P450YLM-A1
7.20 + 7.20
120 + 120
4.2 + 4.2
44
4.5 + 4.5 ~ 11.6 + 11.6
Inverter
11.6
Galvanized steel sheets
1,450 x 880 x 550
Over-heat protection
R410A x 6.0 kg (14 lbs)
217 (479)
plate type
5.0
2.0
89

Advertisement

loading

This manual is also suitable for:

S seriesWy seriesR2 seriesWr2 series