HOT WATER HEAT PUMPS
228
Power Source
Capacity *1
Power Input
Current Input
COP(kW/kW)
Capacity *2
Power Input
Current Input
COP(kW/kW)
Capacity *3
Power Input
Current Input
COP(kW/kW)
Maximum Current Input *4
Allowable External Pump Head
Outlet Water Temp
Temperature Range
Outdoor Temp
Sound Pressure Level (measured 1m below the unit
in an anechoic room) *1
Inlet
Water Pipe
Diameter and Type
Outlet
External Finish
External Dimension H x W x D
Net Weight
R744
Design Pressure
Water
Water-side
Heat Exchanger
Air-side
Type
Maker
Compressor
Motor Output
Case Heater
Air Flow Rate
FAN
Type x Quantity
Control, Driving Mechanism
Motor Output
HIC (HIC: Heat inter-changer) Circuit
High Pressure Protection
Inverter Circuit
Protection
Compressor
Fan Motor
Defrosting Method
Refrigerant
Type x Original Charge
QAHV-N560YA-HPB
3-phase 4-wire 380-400-415V 50Hz
kW
40
Btu/h
136480
kW
10.31
A
17.8-16.9-16.3
3.88
kW
40
Btu/h
136480
kW
10.97
A
20.0-19.0-18.3
3.65
kW
40
Btu/h
136480
kW
11.6
A
20.4-19.4-18.7
3.44
A
28.8-27.4-26.4
77kPa
55–90°C
D.B.
-25~43°C
dB(A)
56
mm(in.)
19.05(Rc 3/4"), screw pipe
mm(in.)
19.05(Rc 3/4"), screw pipe
Acrylic painted steel plate
<MUNSELL 5Y 8/1 or similar>
mm
1837(1777 not including legs) x 1220 x 760
kg(lbs)
400(882)
MPa
14
MPa
1.0
Copper tube coil
Plate fin and copper tube
Inverter scroll hermetic compressor
MITSUBISHI ELECTRIC CORPORATION
kW
11.0
kW
0.045
m3/min
220
L/s
3666
Propeller fan
Inverter-control, Direct-driven by motor
kW
0.92
Copper pipe
High pres.Sensor & High pres.
Switch at 14MPa(643psi)
Overheat and overcurrent protection
Overheat protection
Thermal switch
Auto-defrost mode (Hot gas)
CO
(R744) 6.5kg
2
Optional Parts
Remote
Representative Water
Controller
Temperature Sensor
PAR-W31MAA-J
TW-TH16-E
Notes:
*1.Under Normal heating conditions at the outdoor temp,
16°CDB/12°CWB(60.8°FDB/53.6°FWB),
the
temperature 65°C(149°F), and the inlet water temperature
17°C(62.6°F)
*2.Under Normal heating conditions at the outdoor temp,
7°CDB/6°CWB(44.6°FDB/42.8°FWB), the outlet water tempera-
ture 65°C(149°F), and the inlet water temperature 9°C(48.2°F)
*3.Under Normal heating conditions at the outdoor temp,
7°CDB/6°CWB(44.6°FDB/42.8°FWB), the outlet water tempera-
ture 65°C(149°F), and the inlet water temperature 15°C(59.0°F)
*4.Under Normal heating conditions at the outdoor temp,
7°CDB/6°CWB(44.6°FDB/42.8°FWB), when the unit is set to the
"Capacity Priority" mode through the dry NC-contact.
*Due to continuing improvements, specifications may be sub-
ject to change without notice
*Do not use steel pipes as water pipes.
*Keep the water circulated at all times. Blow the water out of
the pipes if the unit will not be used for an extended period
time.
*Do not use ground water or well water
*Do not install the unit in an environment where the wet bulb
temperature exceeds 32°C
*The water circuit must use the closed circuit
*There is a possibility that the unit may abnormally stop when
it operates outside its operating range. Provide backup (ex.
boiler start with error display output signal (blue CN511 1-3))
for abnormal stop.
UNIT CONVERTER
BTU/h = kW x 3,412
lbs
= kg/0.4536
outlet