Power Up: DLP-507
Page 8 of 10
47. Does BAT DISCHG indicator go off and HIGH RATE CHG/ON indicator light
on BATTERY CHARGER?
If YES, then proceed to Step 53.
If NO, then continue with Step 48.
48. Replace BATTERY CHARGER.
Response:
49. Press HIGH RATE CHG/ACTIVATE pushbutton on BATTERY CHARGER
after BAT DISCHG indicator goes off.
Response:
50. Does BAT DISCHG indicator go off and HIGH RATE CHG/ON indicator light
on BATTERY CHARGER?
If YES, then proceed to Step 53.
If NO, then continue with Step 51.
BAT DISCHG indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If BAT DISCHG indicator remains lighted for more than 4
minutes, BCU PMN (or P/M) and ADU NE indicators will also
light.
When BAT DISCHG indicator goes off, the HIGH RATE
CHG/ON indicator will light and, if BCU PMN (or P/M) and
ADU NE indicators are lighted, they will go off after 4 min-
utes.
The HIGH RATE CHG/ON indicator will go off after a period
of time determined by charge state of batteries.
BAT DISCHG indicator will light and remain lighted for a
period of time determined by charge state of batteries.
If BAT DISCHG indicator remains lighted for more than 4
minutes, BCU PMN (or P/M) and ADU NE indicators will also
light.
When BAT DISCHG indicator goes off, the HIGH RATE
CHG/ON indicator will light and, if BCU PMN (or P/M) and
ADU NE indicators are lighted, they will go off after 4 min-
utes.
The HIGH RATE CHG/ON indicator will go off after a period
of time determined by charge state of batteries.
363-205-401
Issue 7, March 1997