Power Up: DLP-504
Page 4 of 6
12.
!
DANGER:
A high discharge current is present at connector head if TESTING
indicator is lighted. Batteries must not be connected or disconnected
when TESTING indicator is lighted.
NOTE:
This test must run for a full 15 minutes to be valid or until all batteries
indicate REPLACE. The STOP button should only be used if a problem
occurs during the test, if the test is to be terminated early because of loss
of AC power, or if all batteries indicate REPLACE. The
START/CONTINUE button is used to continue the test if no problem is
found.
Depress 197A test set START/CONTINUE button.
Response:
13.
NOTE:
If one, two, or three, but not all, batteries show REPLACE during the test
period, the remaining batteries still must be tested for the full 15 minutes.
Does test set show REPLACE for all batteries within the 15-minute test period
shown on TIME display?
If YES, then continue with Step 14.
If NO, then proceed to Step 15.
14.
!
DANGER:
A high discharge current is present at connector head if TESTING
indicator is lighted. Batteries must not be connected or disconnected
when TESTING indicator is lighted.
Depress test set STOP button.
Response:
Proceed to Step 17.
At 197A test set, TESTING indicator is lighted, READY indi-
cator is off, and TIME display is counting time.
STOP indicator on test set lights
363-205-401
Issue 7, March 1997