Parameter
This time is expressed in ms.
This field is not used by the "IO", "TIC" and "SMA-
Net" protocols.
For SMA-Net, the value is 3000ms.
SerialNumber
Some devices require a serial number. This is
especially the case for "TIC" devices. This field is
used to indicate it.
It is not used by the "IO" and "Modbus" protocols
Parameters
This field is only used in the following cases:
Manufacturer
This field indicates the device manufacturer. Note
that the concentrator fills in this field
automatically.
For TIC devices, the field is left empty and will be
used in the future.
Model
This field indicates the device model name.
Note that the concentrator fills in this field
automatically.
For TIC devices, the field is left empty and will be
used in the future.
DefFile
This field is used to indicate the definition file that
exactly describes all the variables and data exposed
by the device.
See the specific definition file section (3.1.2.2 -
Connected device definition).
Below is a connected device interface configuration example:
index;interface;name;address;acqPeriod(s);timeout(ms);serialNumber;parameters;category;
model;defFile
IO;;Io;;36000;;;;WebdynSunPM;ioSunPM;WPM00C715_IO.csv
TIC1;;;;600;;041676011381;9600;Meter;;WPM00C715_TIC_LINKY.csv
0;SERIAL1;serial1_52224;0;600;0;2000388220;1;Inverter;WR21TL09;WPM00C715_SMA_Inverter_S
MA_WR21TL09.csv
1;192.93.121.23:502;ethernet_192.93.121.23_502_126;126;600;5000;;1;Inverter;Solar_Inver
ter;WPM00BDE4_SunSpec_inverter_SMA_Solar_Inverter_9301_modbusTCP.csv
Version 2.05
préliminaire
Description
• ModbusTCP devices: used to indicate if
"KeepAlive" messages are sent to keep the
connection open. If the field value is "1", a
regular message is sent. If the field value is
"0", no message is sent.
The default value is 1
• SMA-Net devices: used to indicate the time
between two frames. This time is expressed
in ms.
USER MANUAL – WebdynSunPM
Default value
57