Connected device interface configuration is based on the following parameters:
Parameter
Index
Index for the device to be defined.
This field contains a numeric value representing
the identification number for the device to be
configured.
Each number must be unique, failing which the
device will not be visible in the web interface.
The following index values are also accepted:
Interface
For "IO" or "TIC" devices, this field is not used. It
must be left empty.
For modbus devices, it contains the following
information:
Name
This field describes the name given to the device in
the web interface. This name is also used for MQTT
and the scripts. This is why it is essential that it be
unique in the configuration.
Address
This field is not used for "IO" and "TIC" type
devices.
For "modbus" devices, it contains the device
address on the modbus network. Its value is
therefore from 1 to 240.
For "TIC", "IO" and "SMA-Net" devices, this field is
not used.
AcqPeriod
This field indicates the acquisition frequency.
It is expressed in seconds.
Timeout
Device response timeout configuration. If the
device does not respond within this time limit, the
concentrator considers the request to have failed.
Version 2.05
préliminaire
Description
• IO: is used to indicate that the definition
file is for the concentrator IO
• TIC1: is used to indicate that the definition
file is for a TIC type device.
• SERIAL1: the device is connected to serial
port 1
• SERIAL2: the device is connected to serial
port 2
• SERIAL3: the device is connected to serial
port 3
• "IP address" the device is of the modbus
TCP type and is accessible at the indicated
IP address
• "IP address-Port:" the device is of the
modbus TCP type and is accessible at the
indicated IP address at the indicated TCP
port number.
USER MANUAL – WebdynSunPM