Huawei FusionModule800 Quick Manual page 58

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

3.6
Commissioning Sensors
Item
Check Method
Smoke
Simulate a smoky environment
Detector
under the smoke sensor.
WLDS900
Immerse the water detection
Water Sensor
cable in water.
Electrode
Immerse the two contacts of the
Water Sensor
electrode water sensor in water.
T/H Sensors
Check the running information
(BOM
about T/H sensors on the WebUI.
Number:
02312PBL)
Set T/H sensor alarm thresholds.
In-Room
Method 1: Attempt to open the
Access
door using the configured
Control
authentication mode.
System
For example, if you select Card,
password and fingerprint for the
authorization mode, the door can
be opened only after you swipe
an authorized card first, enter the
authorized password (press # to
confirm the password), and then
scan the fingerprint.
Method 2: On the WebUI, choose
Monitoring > Aisle > Access
Actuator Group > Access
Actuator
open the door remotely.
In-Room Exit
Open the door by pressing the
Button
exit button when the aisle door is
properly closed.
In-Room
When the room door is properly
Emergency
closed, short circuit the wiring
Door Release
terminals NO and COM on the
Button
emergency door release button.
n
, and click Controls to
Normal Connection Status
Smoke DI alarm is displayed on the active
alarm screen of the app or on the WebUI.
Leak DI alarm is generated on the active
alarm screen of the app or on the WebUI.
Leak DI alarm is generated on the active
alarm screen of the app or on the WebUI.
Choose Monitoring > Aisle > T/H Sensor
Group > T/H Sensor
check the current T/H and NTC information of
the cabinet.
Choose Monitoring > Aisle > T/H Sensor
Group > T/H Sensor
Parameters, and set High temperature
alarm threshold, Low temperature alarm
threshold, High humidity alarm threshold,
and Low humidity alarm threshold as
required.
The default values of High temperature
alarm threshold, Low temperature alarm
threshold, High humidity alarm threshold,
and Low humidity alarm threshold are
30.0°C, 5.0°C, 85.0% RH, and 15.0% RH,
respectively.
For method 1: The aisle door is opened
successfully.
For method 2: After you choose Query >
Access Event on the WebUI, you can view the
type of this access control event.
The room door is opened properly.
The room door is opened properly.
55