Huawei FusionModule800 Quick Manual page 2

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

Overview
Item
Cabinet dimensions
(H x W x
D)/Reference net
weight
Indoor unit (with a
control unit)
dimensions (H x W x
D)/Net & gross
weight
Outdoor unit
dimensions (H x W x
D)/Net & gross
weight
Bearing capacity
Levelness
Equipment room
height
Equipment room area
Door size
Elevator
Power supply
Floor drain
Grounding
Water port
Specifications
IT cabinet: 2000 mm x 600 mm x 1350 mm/160 kg
Converged Cabinet: 2000 mm x 600 mm x 1350 mm/410 kg
Battery cabinet (deployed inside the aisle containment): 2000 mm x
600 mm x 1350 mm/160 kg
Battery cabinet (deployed outside the aisle containment): 2000 mm
x 600 mm x 1100 mm/1200 mm/140 kg
Network cabinet: 2000 mm x 800 mm x 1350 mm/160 kg
With water pump, heater, and humidifier: NetCol5000-A013: 486
mm x 442 mm x 800 mm/52.6 kg & 70 kg
With water pump, but without heater and humidifier: NetCol5000-
A013: 486 mm x 442 mm x 800 mm/49.4 kg & 66.8 kg
NetCol500-A018: 966 mm x 1057 mm x 339 mm/83 kg & 99 kg
NetCol500-A020: 1327 mm x 966 mm x 320 mm/101 kg & 114 kg
NetCol500-A021: 1350 mm x 1270 mm x 730 mm/205 kg & 235 kg
Standard live load of the main equipment room: 8-12 kN/m² (If the
battery cabinet is placed inside the smart module, use the standard
live load of the main equipment room as a reference.)
Suspended load of the main equipment room: 1.2 kN/m²
Standard live load of the battery room: 16 kN/m²
Allowed deviation: 3/2000 mm
≥ 2.6 m
8–30 m²
Height > 2.2 m; width > 0.9 m
Elevator bearing capacity > 1.5 t
Elevator internal size: height > 2.4 m, depth > 1.4 m
Elevator door size: height > 2.2 m; width > 0.9 m
380 V AC/400 V AC/415 V AC, 3 Ph, 50 Hz/60 Hz
DN50 or larger, made of cast iron or stainless steel
A general ground bar is configured in the Converged Cabinet. The
general ground point in each cabinet connects to the general ground
bar in the Converged Cabinet. The general ground bar in the
Converged Cabinet connects to the floor ground bar or collective
ground bar.
Condensate drain outlet: for draining condensate from the smart
cooling product.
Humidifier water pipe port: Connects to external water pipes to supply
water to the humidifier.
1
Copyright © Huawei Technologies Co., Ltd.
2021. All rights reserved.