2
Outdoor Unit Installation Scenario
If the outdoor unit is placed higher than the indoor unit, the maximum height deviation
between them should be less than or equal to 30 meters. Install an oil trap every 5–6 meters
in the vertical direction along the gas pipe.
If the indoor unit is placed higher than the outdoor unit, the maximum height deviation
between them should be less than or equal to 8 meters.
Layout of upward piping
(1) Oil trap

Hardware Installation

1
(Optional) Removing Aisle Containments
1. Remove the PAD cable.
2. Remove the gas springs.
(2) Tilted gas pipe
Layout of downward piping
(3) Indoor unit
3. Remove the cabinet doors.
3
(4) Tilted liquid pipe