Installing A Camera - Huawei FusionModule800 Quick Manual

Smart small data center
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

A: Position for installing the T/H sensor for the NetCol at the bottom of the Converged Cabinet,
28 U
B: Position for installing the T/H sensor for the NetCol on the top of the Converged Cabinet, 14 U
C: Position for installing the T/H sensor for the NetCol at the bottom of the IT cabinet, 28 U
D: Position for installing the T/H sensor for the NetCol on the top of the IT cabinet, 14 U
1. Attach a T/H sensor to the IT cabinet door frame.
2. Set the T/H sensor address to 11.
3. Connect the T/H sensor monitoring cable.
The default addresses of T/H sensors purchased from Huawei are 1.
After the addresses are set, set Cold-aisle sensor to Enable on the ECC800 WebUI.
Otherwise, the T/H sensors will not work. Path: Monitoring > Cooling > NetCol5000-A1 >
Running Parameters > Temp/Hum Sensor Parameters.
14.7

Installing a Camera

1. Secure a camera to the mounting
plate.
3. Connect one end of a network cable to
the Ethernet port on the camera and the
other end to any network port on the
smart ETH gateway (with PoE power
supply).
4. Adjust the monitoring coverage.
5. Install the inner cover.
6. Install the front cover.
Addr
DIP Switch Sequence No.
ess
1
2
3
11
ON
ON
OFF ON
4
5
6
OFF OFF
2. Secure the mounting plate to the top
of the front door of the end cabinet.
37

Advertisement