9. On the Controls > Control Information page, choose Diagnostic Mode > Exit and click
Submit.
Outdoor Ambient Temperature
Below 15°C
15–35°C
35–45°C
Above 45°C
3
Management System Power-On Commissioning
3.1
Preparations and WebUI Login
1. Connect a network cable between the PC network port and the WAN_1 port (protected by a
security mechanism) on the ECC800.
2. Configure the PC IP address and the WAN_1 IP address in the same network segment.
3. Set LAN parameters.
4. Set Internet Explorer parameters.
5. Log in to the ECC800 WebUI.
Change the initial password after the first login.
3.2
Preparations and App Login
1. Log in to HUAWEI App Store (http://a.vmall.com/), search for FusionModule, and tap
Download.
2. Install the app.
3. Enable the WiFi function on the ECC800 WebUI.
4. Log in to the app.
3.3
Performing Startup Password Authentication
1. Authenticate the startup password on the WebUI.
a) Log in to the ECC800-Pro WebUI as an administrator.
b) Record the values of Barcode and Verify Code in the displayed Startup Password dialog
box.
c) Within 24 hours, inform Huawei technical support of Barcode and Verify Code to obtain
the password. After obtaining the password, enter the password in the Password text box
and click Submit to complete the authentication of the startup password.
2. Use the Service Expert app to authenticate the startup password.
a) Log in to Huawei AppGallery (http://a.vmall.com/), search for Service Expert, and tap
Download to obtain the installation package.
b) Install the app.
c) Hold down the SW button on the ECC800-Pro for less than 3s to enable the WiFi function.
d) Use the Service Expert app to authenticate the startup password.
3.4
Setting the Date and Time
1. Choose System Settings > System Parameters > Time.
2. Set the time zone, date, and time or click Obtain Local Time, and click Submit.
3.5
Creating a Micro-Module Plan View
1. Choose Home > Plan View, click Create Micro-Module in Micro-Module View and set the
layout and device quantity based on the actual micro-module scenario.
2. Drag the icons of registered devices and devices on the cabinet list to appropriate positions in
the layout to create a micro-module plan view.
Proper Discharge Pressure Range
1.5–2.5 MPa
1.5–3.1 MPa
2.5–3.8 MPa
3.1–4.0 MPa
56