Mandik FDMB Manual page 81

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

Installation frame R6 is suitable for:
● Installation outside solid wall/ceiling construction with cement lime plates
On the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and air
proofs the gap between installation frame and damper body.
● Installation frame:
● Fasteners:
● d = (D +100 mm)
80
≤ 300
≤ 300
Screw
(min. 4x80)
Screw
20
(min. 4x80)
20
≤ 300
≤ 300
POSITION:
1
Damper with installation frame R6
2
Cement lime plates min. thickness 40 mm
(min. density 450 kg/m )
3
Cement lime prisms min. thickness 40 mm
(min. density 450 kg/m )
cement lime plates
galvanized plate
40
20
Screws has to be fixed in wall/ceiling
20
construction. (If it is needed use steel
bracket).
Screw
40
(min. 4x80)
40
≤ 300
≤ 300
* min. 110 - Concrete/ min. 125 - Aerated concrete
150*
≤ 300
20
20
≤ 300
Screw
20
(min. 4x80)
20
≤ 300
≤ 300
80
Screw
(min. 4x80)
Screw
40
(min. 4x80)
40
≤ 300
≤ 300