Download Print this page

Mandik FDMB Manual page 72

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

Installation frame E1 is suitable for:
● Solid wall construction
● Gypsum wall construction
● Solid ceiling construction
On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacity
and air proofs the gap between damper body and installation frame and between installation frame and
wall construction.
● Gypsum wall construction has to be installed according manufacture requirements.
● Installation frame:
● Fasteners:
● a x b = (A + 85 mm) x (B + 85 mm)
≥ 100
150*
* min. 110 - Concrete/ min. 125 - Aerated concrete
cement lime plates
galvanized plate
>100
≥125
≥125
≥ 50
POSITION:
1
Fire damper FDMB with installation frame E1
2
Holder with screws
3
Gypsum plate
4
Mineral stone wool min. density 140 kg/m
5
Fire protection mastic min. thickness 1 mm
71
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
It is possible to use
≥ 100
corresponding number of
holes and screws
Dimensions
A,B ≤ 400
400 < A,B ≤ 800
800 < A ≤ 1000
Number
Number
ZB1
ZH1
1
1
2
2
3
3

Advertisement

loading