Mandik FDMB Manual page 59

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

10 to 50
10
10
D+152
Number
Dimensions
X1
D ≤ 400
4
400 < D ≤ 800
8
800 < D ≤ 1000
12
POSITION:
1
Fire damper FDMB
2
Fire damper FDMB with installation frame R1, R2
3
Mortar or gypsum
4
Mineral stone wool min. density 140 kg/m
5
Holder
6
Holder L
10
10
D+142
It is possible to use
corresponding number of
Number
Number
holes and screws
Y
Z1
8
2
16
4
24
6
3
≥ 100
≥ 100
It is possible to use
corresponding number of
holes and screws
Gap between frame and damper body and frame and
construction must be filled by glue (PROMAT K84).
Wool is fixed to installation frame and construction by fire
protection mastic.
58
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.