Download Print this page

Mandik FDMB Manual page 64

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

20
Installation opening has to be reinforced by
profile (UW, CW). Profil is fixed by screws
≥3,5 mm with corresponding length.
Distance between screws ≤200 mm.
20
A = max. 1000 mm
POSITION:
1
Fire damper FDMB with
Installation frame E1, R1
2
Gypsum plate
3
Fire resistant insulation
4
Mineral stone wool min.
density 140 kg/m
5
Flange connection
≥ 100
Installation opening has to
≥ 100
be reinforced by profile
(UW, CW). Profil is fixed
by screws ≥3,5 mm with
corresponding length.
Distance between screws
≤200 mm.
20
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 mm)
or a x b = (A + 85 mm) x (2x(B + 85 mm) + 20 mm)
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(D + 141 mm) + 20 mm) x (D + 141 mm)
or a x b = (D + 141 mm) x (2x(D + 141 mm) + 20 mm)
Gap between frame and damper body and frame and
construction must be filled by glue (PROMAT K84)
Fire damper FDMB-C - distance between dampers 104 mm
Fire damper FDMB-K - distance between dampers 160 mm
Flange to flange connection - Up to four dampers can be installed
63
20
Installation opening has to be reinforced by
profile (UW, CW). Profil is fixed by screws
≥3,5 mm with corresponding length.
Distance between screws ≤200 mm.
It is possible to use
corresponding number of
holes and screws
Dimensions
A1,B1,D1 ≤ 400
400 < B1,H1,D1 ≤ 800
800 < B1,D1 ≤ 1260
1260 < B1,D1 ≤ 1600
1600 < B1 ≤ 2000
≥ 100
Installation opening has to
be reinforced by profile
≥ 100
(UW, CW). Profil is fixed
by screws ≥3,5 mm with
corresponding length.
Distance between screws
≤200 mm.
Number
Number
ZB1
ZH1
1
1
2
2
3
3
4
4
5
5

Advertisement