Mandik FDMB Manual page 58

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

≤ 50
≤ 50
≤ B+100
10 to 50
POSITION:
1
Fire damper FDMB
2
Mortar or gypsum
3
Mineral stone wool min. density 140 kg/m
≤ 50
(≥ 100)+20
D-20
≥ 100
(≥ 100)+50
Gap between damper and construction is filled by mortar or
gypsum and mineral wool
Wool is fixed to damper body and construction by fire protection
mastic
Mineral wool thickness = construction thickness + 20 mm or 50 mm
Installation is valid for ceiling construction
3
57
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
≥ 100
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.