These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMB. It is valid for production, designing, ordering, delivery, assembly and operation. 1. Description......................... 2. Design..........................3. Communication and control devices………................. 4. Dimensions, weights and effective area................
Page 3
• Cycling test in class C 10000 acc. to EN 15650 • Corrosion resistant acc. to EN 15650 • ES Certificate of conformity No. 1391-CPR-2020/0136 • Declaration of Performance No. PM/FDMB/01/22/5 • Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b Working conditions...
Page 4
Design with mechanical control Design with mechanical control with a thermal protective fuse which actuates the shutting device, after the nominal start temperature 72°C has been reached. Automatic initiation of the shutting device is not activated if the temperature does not exceed 70°C. In case that other start temperatures are required, thermal fuses with nominal start temperature +104°C or +147°C can be supplied (this requirement must be specified in the order).
Page 5
1(COM) - black wire 2(NC) - gray wire 4(NO) - blue wire AC 230V / 5A This limit switch is possible to connect in following two versions: IP 67 if the arm is moving … connect wire 1+2 -25°C … +120°C if the arm is moving …...
Page 6
Design with actuating mechanism The damper are equipped by Belimo actuators with spring return and thermoelectric activation device of BFL, BFN or BF depending on the damper size (furher mentioned as „actuators“). After being connected to power supply AC/DC 24V or 230V, the actuating mechanism displaces the damper blade into operation position "OPEN"...
Page 7
S1 S2 <5° <80° Nominal voltage AC 24 V 50/60 Hz AC 230 V 50/60 Hz DC 24 V Power consumption - motoring 3,5/5 W 2,5/4 W - holding 1,1/2,1 W 0,8/1,4 W Dimensioning 6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms) Protection class Degree of protection...
Page 8
Nominal voltage AC 24 V 50/60 Hz AC 230 V 50/60 Hz DC 24 V Power consumption - motoring - holding Dimensioning 10 VA (Imax 8,3 A @ 5 ms) 12,5 VA (Imax 500 mA @ 5 ms) Protection class Degree of protection IP 54 Running time - motor...
Page 9
RS-Bus communication relay contact relay contact 24 V DC...
Page 10
Design with the communication and supply device BKN 230-24 and the actuating mechanism BF 24-TN-ST (BFL 24-T, BFN 24-T). It simplifies electrical wiring and interconnection of fire flap valves. It facilitates on site check and enables central control and checks of fire damper by means of a simple 2-conductor wiring.
Page 11
Bridge has been installed by the manufacturer. If needed, it can be removed ad replaced with a thermoelectric starting mechanism. If terminals 1 and 2 are not interconnected, safety function is initiated. Bridge can be used only for starting and without BKS24… ! Two conductor wiring to BKS24 Design .61 with communication and supply device can be complemented with smoke detector ORS 142 K.
Page 12
Design .60 with communication and supply device can be complemented with smoke detector ORS 142 K. For supply and comunnication is used BKN 230-24-MOD, which is used together with the BF 24TN-ST (BFL 24T-ST, BFN 24T-ST) for communication with control systems using the Modbus RTU or BACnet MS / TP protocol.
Page 13
External smoke detector, +24 V, max. 50 mA External smoke detector, control input BKN Direct Control, override control input Design with the communication and supply device BKN 230-24MP and actuating mechanism BF 24TL-TN-ST for connection to MP-Bus. BKN 230-24MP supplies to intelligent actuating mechanisms of fire dampers BF 24TL-TN-ST decentrally needed power supply.
Page 14
Actuating mechanism Nominal voltage AC 24 V 50/60Hz DC 24 V Power consumption - motoring - holding Dimensioning 10 VA (Imax 8,3 A @ 5 ms) Protection class Degree of protection IP 54 Running time - motor 120 sec - spring return ~ 16 sec Ambient temperature -30°C …...
Page 15
additional external conntact, net MP-Bus eg. fire smoke detector PC Tool AC230 V Nominal voltage AC 230 V 50/60Hz Power consumption 14 W (including actuating mechanism) Dimensioning 16 VA (including actuating mechanism) Protection Class Degree of protection IP 40 Ambient temperature -30°C …...
BKS 24-1B communication and control device is used for control and checks of fire dampers with the BF 24-TN-ST (BFL 24-T-ST, BFN 24-T-ST) actuating mechanism in conjunction with the BKN 230-24 supply and communication device. BKS 24-1B receives information about the situation of the fire damper through the BKN 230-24 supply and communication device and issues controlling commands.
Page 17
Nominal voltage AC 24 V 50/60Hz Power consumption 2,5 W (operating position) Dimensioning 5 VA Protection Class Degree of protection IP 30 Ambient temperature 0 … +50°C 11-pole connector ZSO-11, it is not part of BKS24-1B, Connection ZSO-11 is 11-pole screw terminal 11 x 1,5 mm² BKS 24-9A communication and control device is used for group control and checks of 1 to 9 fire dampers with the actuating mechanism BF 24-TN-ST (BFL 24-T-ST, BFN 24-T-ST) in connection with the supply and communication device BKN 230-24.
Page 18
Nominal voltage AC 24 V 50/60Hz Power consumption 3,5 W Dimensioning 5,5 VA Protection Class Degree of protection IP 30 Ambient temperature 0 … +50°C Connection terminal 2 x 1,5 mm²...
Page 19
Dimensions (60+X)/2 B-X* B+60 B+60 * X=14 (A<160 or B<160) * X=23 (AxB≤500x400) 37,5 * X=36 (AxB>500x400) ** Some countries 20mm flanges (A+40 resp. B+40) Position: Damper casing Mechanics Damper blade Inspection hole covering Sensor sticker Hole for camera (60+X)/2 B-X* B+60 B+60...
Page 26
Blades overlaps Act. mechanism side "a" Tab. 4.2.1 Side without act. mechanism "c" Tab. 4.2.1 For the design .60 (with BKN supply and communication device) add to weight of the damper with an actuating mechanism (from the Tab 4.2.1.) the weight of BKN…0,5 kg. Dampers can be supplied on the customer´s demands in all subdimension of the above men- tioned range.
Page 27
Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions. Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the back-to-back piping to the damper is absolutely excluded.
Page 28
The control mechanism has to be protected (covered) against damage and pollution during installation process. All fire dampers has to be closed during installation process. The damper body should not be deformed in the course of bricking in. Once the damper is built in, its blade should not grind on the damper body during opening or closing.
Page 29
EIS 120 - 500 Pa Mortar or gypsum EIS 120 EIS 90 Stuffing box with fire protection mastic EIS 60 EIS 60 Fire protection foam with stucco plaster EIS 45 EIS 30 Battery - mortar or gypsum EIS 90 Installation next to wall - mortar or gypsum and mineral wool EIS 90 Stuffing box with fire protection mastic and cement lime plate EIS 90...
Page 30
≥ 100** ≤ 75* * Around the perimeter Position: Fire damper Solid wall construction Mortar or gypsum Duct ≥ 100 * Around the perimeter ≥ 20* ≤ 75* Used materials - example: Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50 Position: Promastop - P, K, Hilti CFS-CT Fire damper...
Page 31
≥ 20 ≤ 75 Used materials - example: HILTI CFS-F FX - EIS 60 ≥ 100 Position: PROMAFOAM-C - EIS 45 Fire damper SOUDAL, Soudafoam FR-B1 - EIS 30 Solid wall construction DenBraven, Fire protection foam - EIS 30 Fire protection foam Stucco plaster Duct...
Page 32
The gap 94 mm between dampers can be filled by mineral stone wool min. density 140 kg/m³. Wool is fixed to damper body by fire protection mastic. ≥ 94 ≥ 100 ≤ 75 The gap 94 mm between dampers can be filled by mineral stone wool min.
Page 33
≤ 75 ≤ 75 ≤ 75 ≤ A+150 ≥ 100 (≥ 100)+20 ● Gap between damper and construction is filled by mortar or Position: gypsum and mineral wool Wool is fixed to damper body and construction by fire protection ● Fire damper mastic Mortar or gypsum...
Page 34
≥ 100 ≥ 50* ≤ 75* * Around the perimeter Ensure symmetry with rod location 25 (±5) ≤ 300 Threaded rod M8, 2x nut, 2x washer ≤ 300 (rod length for 100mm wall is approx 150mm) 25 (±5) Seal the gap between plates with HILTI CFS-S ACR mastic ≤...
Page 35
≥ 100 ≥ 100 Apply HILTI CFS-S ACR to the entire surface ≥ 100 Position: Fire damper Installation frame Solid wall construction...
Page 36
B+60 to 800 A+60 to 800 ≥ 100 Position: Fire damper Solid wall construction Used materials - example: Fire resistant board Hilti CFS-CT B 1S 140/50 Fire stop coating thickness 1 mm Hilti CFS-CT Duct PROMATECT-H Protective cladding boards - (not part of the damper) for AxB ≤...
Page 37
≥ 100 ≥ 100 It is possible to use corresponding number A = max. 1000 mm of holes and screws Number Number Dimensions Position: Fire damper with installa- ● Installation opening dimensions A1,B1 ≤ 400 a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 tion frame E1 400 <...
Page 38
* Around the perimeter ≤ 75* Position: Fire damper Solid wall construction Mortar or gypsum Insulation board made of stone wool, with a surface treatment of aluminum Used materials - example:** foil, density 66 kg/m³ 4 Isover Ultimate Protect SLAB 4.0, th. 80 mm ALU1 Duct Apply ISOVER Protect BSK glue on Insulation materials can be replaced by another approved fire sealing...
Page 39
≥ 50* ≤ 75* L=Min. 400 L=Min. 100 T=120 * Around the perimeter T=120 L=variable*** T=60 ≥ 100 Ensure symmetry with rod location 25 (±5) ≤ 300 Threaded rod M8, 2x nut, 2x washer ≤ 300 (rod length for 100mm wall is approx 150mm) 25 (±5) Seal the gap between plates with HILTI CFS-S ACR mastic...
Page 40
Apply HILTI CFS-S ACR to the entire surface * Around the perimeter ≤ 75* ≥ 100 Position: Fire damper Installation frame E6 Solid wall construction Cement lime plate - all parts are glued with glue Promat K84 and secured by screws. Duct...
Page 41
≥ 100** Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≤ 75* * Around the perimeter Position: Fire damper Gypsum plate Mineral wool (type depending on the type of construction) Mortar or gypsum Duct ≥...
Page 42
Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≥ 20 ≤ 75 Used materials - example: HILTI CFS-F FX - EIS 60 PROMAFOAM-C - EIS 45 Position: SOUDAL, Soudafoam FR-B1 - EIS 30...
Page 43
The gap 94 mm between dampers can be filled by mineral stone wool min. density 140 kg/m³. Wool is fixed to damper body by fire protection mastic. ≥ 94 ≥ 100 Installation opening has to be reinforced by steel U- profile.
Page 44
≤ 75 ≤ 75 Installation opening has to be reinforced by steel U- profile. Profile is fixed by ≤ 75 screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≤ A+150 ≥ 100 (≥ 100)+20 ● Gap between damper and construction is filled by mortar or Position: gypsum and mineral wool ●...
Page 45
Installation opening has to ≥ 100 be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≥ 50* ≤ 75* * Around the perimeter Ensure symmetry with rod location 25 (±5) ≤...
Page 46
Installation opening has to Installation opening has to be reinforced by steel U- be reinforced by steel U- profile. Profile is fixed by profile. Profile is fixed by screws ≥3,5 mm with corre- screws ≥3,5 mm with corre- sponding length. Distance sponding length.
Page 47
B+60 to 800 Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. A+60 to 800 ≥ 75 Position: Fire damper Gypsum plate Mineral wool (type depending on the type of construction) Used materials - example: Fire resistant board Hilti CFS-CT B 1S 140/50...
Page 48
Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. B+60 to 800 A+60 to 800 ≥ 100 Position: Fire damper Gypsum plate Mineral wool (type depending on the type of construction) Used materials - example: Fire resistant board Hilti CFS-CT B 1S 140/50...
Page 49
≥ 100 Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≥ 100 Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length.
Page 50
Position: Fire damper Installation frame E5 * min. 110 - Concrete/ min. 125 - Aerated concrete Solid ceiling construction Wall with possibility of ceiling movement...
Page 51
Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- * Around the perimeter sponding length. Distance between screws ≤200 mm. ≤ 75* Position: Fire damper Gypsum plate Mineral wool (type depending on the type of construction) Mortar or gypsum Insulation board made of stone wool,...
Page 52
Installation opening has to be reinforced by steel U- profile. Profile is fixed by screws ≥3,5 mm with corre- sponding length. Distance between screws ≤200 mm. ≥ 50* ≤ 75* L=Min. 400 L=Min. 100 * Around the perimeter T=120 L=variable*** T=120 T=60 ≥...
Page 53
≤ 75** Position: Fire damper Solid ceiling construction * min. 110 - Concrete/ min. 125 - Aerated concrete Mortar or gypsum Duct ** Around the perimeter ≥ 20 ≤ 75 * min. 110 - Concrete/ min. 125 - Aerated concrete Used materials - example: Position: Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50...
Page 54
The gap 94 mm between dampers can be filled by mineral stone wool min. density 140 kg/m³. Wool is fixed to damper body by fire protection mastic. ≥ 94 ≤ 75** The gap 94 mm between dampers can be filled by mineral stone wool min.
Page 55
≥ 50** ≤ 75** Ensure symmetry with rod location 25 (±5) ≤ 300 ≤ 300 Threaded rod M8, 2x nut, 2x washer (rod length for 100mm wall is approx 150mm) 25 (±5) Seal the gap between plates with HILTI CFS-S ACR mastic ≤...
Page 56
Apply HILTI CFS-S ACR to the entire surface Position: Fire damper Installation frame * min. 110 - Concrete/ min. 125 - Aerated concrete Solid ceiling construction...
Page 57
B+60 to 800 A+60 to 800 Position: * min. 110 - Concrete/ min. 125 - Aerated concrete Fire damper Solid ceiling construction Fire resistant board Used materials - example: Fire stop coating thickness 1 mm Hilti CFS-CT B 1S 140/50 Duct Hilti CFS-CT Protective cladding boards - (not part of the damper)
Page 58
* min. 110 - Concrete/ min. 125 - Aerated concrete It is possible to use A = max. 1000 mm corresponding number of holes and screws Number Number Position: Dimensions Fire damper with installa- ● Installation opening dimensions A1,B1 ≤ 400 tion frame E1 a x b = (2x(A + 85 mm) + 20 mm) x (B + 85...
Page 59
≤ 75** L=Min. 100 T=120 L=variabel**** T=60 L=Min. 400 T=120 * min. 110 - Concrete/ min. 125 - Aerated concrete ** Around the perimeter Used materials - example:*** Rockwool Conlit Ductrock EIS 90, th. 60 mm Stuffing box, fire protection mastic, cement lime plate and insulation materials can be replaced by another approved fire Position: sealing system for damper installation with equivalent material...
Page 60
≤ 750 ≤ 100 Position: Fire damper Solid ceiling construction Concrete B20 * min. 110 - Concrete/ min. 125 - Aerated concrete Rebar Duct ** Around the perimeter Apply HILTI CFS-S ACR to the entire surface ≤ 750 ≤ 100 Position: Fire damper Solid ceiling construction...
Page 61
≤ 75** Apply HILTI CFS-S ACR to the entire surface Position: Fire damper Installation frame E6 Solid ceiling construction * min. 110 - Concrete/ min. 125 - Aerated concrete Cement lime plate - all parts are glued with ** Around the perimeter glue Promat K84 and secured by screws.
Page 62
ShaftWall provides a lightweight, fire resistant structure to protect elements in confined spaces wherever access is limited to one side only. The system provides a protective structure which can be incorporated at an early stage of the construction without the need for scaffolding. The structure is composed of steel profiles (Gypframe) and plasterboard (Gyproc).
Page 63
* Depending on wall min. 30 max. 400 Position: Fire damper Weichschott / Ablative Coated Batt ● Damper can be installed Fire resistant mastic - fill the gap on both sides of the on either side of the wall. fire separation construction and around the perime- ter of penetration and damper body.
Page 65
Installation frame E1 is suitable for: ● Solid wall construction ● Gypsum wall construction ● Solid ceiling construction On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between damper body and installation frame and between installation frame and wall construction.
Page 66
Installation frame E2 is suitable for: ● Solid wall construction ● Solid ceiling construction Damper is on the body equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between damper body and steel cartridge. ● Gypsum wall construction has to be installed according manufacture requirements. ●...
Page 67
Installation frame E3 is suitable for: ● Gypsum wall construction Damper is on the body equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between damper body and cement lime cartridge. On the outside is cement lime cartridge equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between cement lime cartridge and construction.
Installation frame E4 is suitable for: ● Installation on solid wall/ceiling construction ● Installation on gypsum wall construction ● Installation outside solid ceiling constructions with concrete On the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between installation frame and damper body.
Page 69
Installation frame E5 is suitable for gypsum wall construction with ceiling movement possibility. Distance of movement “x”. On the inside and outside is installation frame equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between damper body and installation frame and between installation frame and wall construction.
Page 70
Installation frame E6 is suitable for: ● Installation outside solid wall/ceiling construction with cement lime plates On the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and air proofs the gap between installation frame and damper body. ●...
Page 71
For dampers with A ≥ 800 and damper placement outside wall construction is necessary to use reinforcement VRM-B. Insert part A, B on body of fire damper in correct position Lock screw C It has to be done on each corner of VRM-B 1) Cut the groove for profil U25x40x25 2) Insert profile into groove 3) Fix profile...
Page 72
Mounting to the ceiling wall Position: ² Threaded rod M8 – M20 36,6 Washer 84,3 Coupling Nut Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm)
Page 73
Fixing fire damper to the wall with stuffing box (stone wool + mastic) Position: Solid wall construction Gypsum wall construction Fire damper Duct Stuffing box (stone wool+mastic) Illustrative example of duct anchoring Fixing element/steel holder for connecting damper to the wall (recommended type) Nut M8 with anchor Screw with hexagon head 10 Installation hols...
Page 74
Fixing fire damper to the ceiling with stuffing box (stone wool + mastic) Position: Solid ceiling construction Fire damper Duct Stuffing box (stone wool+mastic) Fixing element/steel holder for connecting damper to the wall (recommended type) Nut M8 with anchor Installation hols Screw M6x10+Nut M6 The method of attachment must follow the minimum requirements for attachment and connection of ductwork in accordance with national regulations.
Page 75
Damper assembly procedures must be done so as all load transfer from the fire separating constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the back-to-back piping to the damper is absolutely excluded.
Page 76
The damper must not be suspended or anchored. The duct must be anchored after national rules, like in fig. 85 - as an example. It can be suspended by using threaded rods and a mounting profiles. Load the suspension system depend on weight of the fire damper. Damper can be suspended from the ceiling construction or supported above the ceiling construction.
Fire dampers installed remote from the wall must be suspended. The duct must be suspended on both sides of damper after national rules. Duct between fire damper and fire separating construction must be suspended by using threaded rods and mounting profiles, or another anchoring system according national standards. Load the suspension system depend on weight of the fire damper and duct system.
Pressure loss calculation [Pa] presure loss [m.s ] air flow speed in nominal damper section [kg.m ] air density coefficient of local pressure loss for the nominal damper section (see Tab. 11.1.1.) Determination of pressure loss by using diagram = 1,2 kg.m...
Page 80
Level of acoustic output corrected with filter A. + 10 log(S) + K [dB(A)] level of acoustic output corrected with filter A [dB] level of acoustic output L related to the 1 m² section (see Tab. 12.3.1.) [m²] duct cross section [dB] correction to the weight filter A (viz Tab.
Damper bodies are supplied in the design made of galvanized plate without any other surface finishing. Damper blades are made of fire resistant asbestos free boards made of mineral fibres. Control devices of dampers has cover from mechanically resistant and standing plastic and rest of the parts is galvanised without further surface treatment.
The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjustment. Dampers are transported by box freight vehicles without direct weather impact, there must not occur any sharp shocks and ambient temperature must not exceed +40°C. Dampers must be protected against mechanic damages when transported and manipulated.
Page 84
Before entering the dampers into operation after their assembly and by sequential checks, the following checks must be carried out. Visual inspection of proper damper integration , inside damper area, damper blade, contact surfaces and silicon sealing. Check of thermal protective fuse and closing mechanism.
Before entering the dampers with actuating mechanism into operation after their assembly and by sequential checks and following checks must be carried out. Check of blade displacement into the breakdown position "CLOSED" can be done after cutting off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical starting mechanism BAT or cutting off the supply from ELECTRICAL FIRE SIGNALISATION).
Page 86
Fire damper Technical specifications Design according Tab. 20.1.1. Building size Nominal size Type Manual and thermal Manual and thermal (Zone 1,2) Manual and thermal with a terminal switch („CLOSED“) Manual and thermal with a terminal switch („CLOSED“) (Zone 1,2) With actuating mechanism BF 230-TN (BFL, BFN 230-T) - voltage AC 230 V With actuating mechanism BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K and with supply device BKN 230-24-MOD (voltage AC 230 V) With actuating mechanism ExMax-15-BF (AC 230 V, AC/DC 24 V) with thermoelectric activation...