TPM 162/22
Version 2023-03-07
FDMQ 120
Fire damper
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
www.mandik.com
MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz

Advertisement

Table of Contents
loading

Summary of Contents for Mandik FDMQ 120

  • Page 1 TPM 162/22 Version 2023-03-07 FDMQ 120 Fire damper Technical Documentation Installation, Commissioning, Operation, Maintenance and Service Manual www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...
  • Page 2: Table Of Contents

    TPM 162/22 These technical specifications state a row of manufactured sizes and models of fire dampers FDMQ 120 It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL.....................................3 Description....................................3 Design.....................................4 Design with manual control ..............................4 Design with spring return actuator............................6 Design with the communication and supply device......................12...
  • Page 3: General

    The return spring of the actuator is actuated when a Dampers have two inspection openings. thermoelectric activation device BAT is activated, when a test FDMQ 120 with spring return actuator FDMQ 120 with manual control Damper characteristics CE certified acc. to EN 15650 ■...
  • Page 4: Design

    ■ ■ with two limit switches signaling of the damper blade Limit switch detail → see page 5 ■ position "CLOSED" and "OPEN". Limit switch Limit switch “OPEN” “CLOSED” Design .80 Page 4 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 5 Class of protection IP 67 CUT-OFF if the arm is moving … connect wire 1+2 ■ Working temperature -25°C … +120°C SWITCH-ON if the arm is moving … connect wire 1+4 ■ Version 2023-03-07 Fire damper - FDMQ 120 Page 5...
  • Page 6: Design With Spring Return Actuator

    "OPEN" to the position "CLOSED" takes maximum 20 sec. Signalisation of damper blade position "OPEN" and ■ "CLOSE" is provided by two microswitches. Thermoelectric activation device BAT Spring return actuator Design .40 and .50 Page 6 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 7 1 m, 2 x 0,75 mm² (BFL 24-T-ST) with 3-pin plug-in connectors - auxiliary switch cable 1 m, 6 x 0,75 mm² (BFL 24-T-ST) with 6-pin plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Version 2023-03-07 Fire damper - FDMQ 120 Page 7...
  • Page 8 1 m, 2 x 0,75 mm² (BFN 24-T-ST) with 3-pin plug-in connectors - auxiliary switch cable 1 m, 6 x 0,75 mm² (BFN 24-T-ST) with 6-pin plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Page 8 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 9 1 m, 2 x 0,75 mm² - auxiliary switch cable 1 m, 6 x 0,75 mm² (BF 24-T-ST) with plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Version 2023-03-07 Fire damper - FDMQ 120 Page 9...
  • Page 10 Max. 95% RH, non-condensing Connection supply Cable 1 m, 2 x 0.5 mm², Betaflam cable heatresistant up to 145°C Duct inside temperature +72 (95/120/140)°C Response temperature thermal fuse Duct outside temperature +72 (95/120/140)°C Page 10 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 11 Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Version 2023-03-07 Fire damper - FDMQ 120 Page 11...
  • Page 12: Design With The Communication And Supply Device

    Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Page 12 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 13 Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Version 2023-03-07 Fire damper - FDMQ 120 Page 13...
  • Page 14 Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Page 14 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 15 1 m with EURO plug - motor (BF ...-Top) 4-pole connector - net MP screw terminals 2-pole - actuating mechanism (variable) screw terminals 2-pole - Top-Line PC-Tool (via ZIP-RS232) 3-pole connector Version 2023-03-07 Fire damper - FDMQ 120 Page 15...
  • Page 16 Cabel 1m, connected to terminals 1, 2 and 4 - motor Actuator connected on the terminals 2 and 5 - communication and supply device BKN Cabel 1m, connected to terminals 1, 2, 4 and 5 Page 16 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 17: Communication And Control Device Bks 24-1B And Bks 24-9A

    Protection Class Degree of protection IP 30 Ambient temperature 0°C … +50°C 11-pole connector ZSO-11, it is not part of BKS24-1B, Connection ZSO-11 is 11-pole screw terminal 11 x 1,5 mm Version 2023-03-07 Fire damper - FDMQ 120 Page 17...
  • Page 18 Nominal voltage AC 24 V 50/60Hz Power consumption 3,5 W Dimensioning 5,5 VA Protection Class Degree of protection IP 30 Ambient temperature 0°C … +50°C Connection terminal 2 x 1,5 mm Page 18 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 19: Dimensions

    B - 10 Damper casing Manual control Damper blade Inspection opening cover Sensor sticker Hole for camera FDMQ 120 with spring return actuator B - 10 X=72 mm (BFL) X=76 mm (BFN) X=83 mm (BF) Damper casing Spring return actuator...
  • Page 20 → see pages 21 to 26 Flange of a damper - INSTALLATION SIDE Values "a" and "c" has to be respected when Flanges of dampers are 30 mm wide with oval hole. projecting following air-conditioning duct. Page 20 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 21: Technical Parameters

    18,5 0,0936 14,5 0,0472 0,0989 15,5 0,0548 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Version 2023-03-07 Fire damper - FDMQ 120 Page 21...
  • Page 22 0,1712 80,5 0,1063 0,1842 100,5 19,5 0,1233 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Page 22 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 23 38,5 0,3596 27,5 30,5 0,2329 0,3859 0,2632 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Version 2023-03-07 Fire damper - FDMQ 120 Page 23...
  • Page 24 710 x 21,5 0,0788 0,3836 22,5 0,0925 0,4146 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Page 24 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 25 71,5 0,9419 36,5 0,2526 71,5 74,5 1,0106 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Version 2023-03-07 Fire damper - FDMQ 120 Page 25...
  • Page 26 72,5 75,5 1,0104 0,5679 75,5 78,5 1,0841 Sizes in increments of 5 mm can be manufactured on request. * For designs with BKN a weight of 0.5 kg must be added. Page 26 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 27: Placement And Installation

    X = recommended min. distance for manual control ≥ 250 mm Y = min. distance for actuator ≥ 200 mm acc. to EN 1366-2 Y = recommended min. distance for manual control ≥ 250 mm Version 2023-03-07 Fire damper - FDMQ 120 Page 27...
  • Page 28 If damper is installed outside a construction it is necessary ■ The fire damper can be installed into a gypsum wall to use reinforcing frame VRM-Q 120 → see page 57 ■ construction with fire classification EI120 or EI 90. Page 28 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 29: Statement Of Installations

    ISOVER Ultimate Protect - Weichschott 40-41 EI 120 (h i↔o) S In solid ceiling construction Mortar or gypsum EN Spec British Gypsum shaftwall EI 120 (v i↔o) S 43-44 construction EI 120 Version 2023-03-07 Fire damper - FDMQ 120 Page 29...
  • Page 30: Installation In Solid Wall Construction

    This installation was tested without supports. Supports are optional, if used, follow the manufacturer's instructions and national standards. ≥ 100 FDMQ 120 Solid wall construction Mortar or gypsum Fixing profile with threaded rod → see pages 45 to 48 Duct Page 30 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 31 ■ 10 Insulation board made of stone wool, min. density 66 kg/m³ if used, follow the manufacturer's instructions and national stan- (e.g. ISOVER Ultimate Protect SLAB 4), th. 60 mm dards. Version 2023-03-07 Fire damper - FDMQ 120 Page 31...
  • Page 32 ■ 12 Insulation board made of stone wool, min. density 66 kg/m³ if used, follow the manufacturer's instructions and national stan- (e.g. ISOVER Ultimate Protect SLAB 4), th. 60 mm dards. Page 32 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 33 Fire resistant mastic - fill the gap on both sides of the fire separation construction and around the perimeter of penetration and damper casing. (e.g. HILTI CFS-S ACR) Fixing profile with threaded rod → see pages 45 to 48 Version 2023-03-07 Fire damper - FDMQ 120 Page 33...
  • Page 34: Installation Outside Solid Wall Construction

    ISOVER Protect BSF casing. (e.g. HILTI CFS-S ACR) VRM-Q 120 → see page 57 (continued on next page) Fixing profile with threaded rod → see pages 45 to 48 Page 34 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 35 ISOVER Protect BSF casing. (e.g. HILTI CFS-S ACR) VRM-Q 120 → see page 57 Fixing profile with threaded rod → see pages 45 to 48 Version 2023-03-07 Fire damper - FDMQ 120 Page 35...
  • Page 36: Installation In Gypsum Wall Construction

    This installation was tested without supports. Supports are optional, if used, follow the manufacturer's instructions and national standards. ≥ 100 FDMQ 120 Gypsum wall construction Mortar or gypsum Fixing profile with threaded rod → see pages 45 to 48 Duct Page 36 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 37 ■ 10 Insulation board made of stone wool, min. density 66 kg/m³ if used, follow the manufacturer's instructions and national stan- (e.g. ISOVER Ultimate Protect SLAB 4), th. 60 mm dards. Version 2023-03-07 Fire damper - FDMQ 120 Page 37...
  • Page 38 ■ 12 Insulation board made of stone wool, min. density 66 kg/m³ if used, follow the manufacturer's instructions and national stan- (e.g. ISOVER Ultimate Protect SLAB 4), th. 60 mm dards. Page 38 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 39 Fire resistant mastic - fill the gap on both sides of the fire separation construction and around the perimeter of penetration and damper casing. (e.g. HILTI CFS-S ACR) Fixing profile with threaded rod → see pages 45 to 48 Version 2023-03-07 Fire damper - FDMQ 120 Page 39...
  • Page 40: Installation Outside Gypsum Wall Construction

    ISOVER Protect BSF casing. (e.g. HILTI CFS-S ACR) VRM-Q 120 → see page 57 (continued on next page) Fixing profile with threaded rod → see pages 45 to 48 Page 40 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 41 ISOVER Protect BSF casing. (e.g. HILTI CFS-S ACR) VRM-Q 120 → see page 57 Fixing profile with threaded rod → see pages 45 to 48 Version 2023-03-07 Fire damper - FDMQ 120 Page 41...
  • Page 42: Installation In Solid Ceiling Construction

    This installation was tested without supports. Supports are optional, if used, follow the manufacturer's instructions and national standards. FDMQ 120 Solid ceiling construction Mortar or gypsum Fixing profile with threaded rod → see pages 45 to 48 Duct Page 42 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 43: Shaft Wall

    +25mm insulation [mm] Gyproc ① 3 x 15 4400 FireLine Gyproc ① 3 x 15 4400 FireLine Gyproc ② 3 x 15 6000 FireLine Gyproc ② 3 x 15 6000 FireLine Version 2023-03-07 Fire damper - FDMQ 120 Page 43...
  • Page 44 ■ All technical specifications and conditions can be found at ■ www.british-gypsum.com Maximum size for FDMQ 120 in shaftwall is 1500mm x 650mm. ■ Damper can be installed on either side of the wall. ■ This installation was tested without supports. Supports are op- ■...
  • Page 45: Suspension Systems

    Washer for M8 - M20 Coupling Nut M8 - M20 Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Version 2023-03-07 Fire damper - FDMQ 120 Page 45...
  • Page 46 Bored plate HILTI MQZ-L or equivalent Dimension elements of the suspension system Washer for M8 - M20 ■ acc. to the weight of a damper → see page 45 Nut M8 - M20 Page 46 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 47 TPM 162/22 Example of fixing FDMQ 120 to the wall In solid wall construction In gypsum wall construction Solid wall construction Gypsum wall construction FDMQ 120 Duct Penetration Fixing profile with threaded rod → see page 46 Fixing element/steel holder for connecting damper to the wall (optional accessories MANDIK, a.s.
  • Page 48 TPM 162/22 Example of fixing FDMQ 120 to the ceiling In solid ceiling construction Solid ceiling construction FDMQ 120 Duct Penetration Fixing profile with threaded rod → see page 46 Fixing element/steel holder for connecting damper to the ceiling (optional accessories MANDIK, a.s. or sheet metal min.
  • Page 49: Example Of Duct Connection

    Steel clamp min. M8 bolts M8 bolt assembly (bolt M8x20 mm, 2 pcs large washer M8, nut M8) * Seal Lock washers M8 Electrically conductive connection of the damping pad with extension piece and duct Version 2023-03-07 Fire damper - FDMQ 120 Page 49...
  • Page 50: Technical Data

    ρ [kg/m air density ξ coefficient of local pressure loss for the nominal damper section → see page 51 Determination of pressure loss by using diagram ρ = 1,2 kg/m Page 50 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 51 0,201 0,199 0,197 0,195 0,193 0,211 0,208 0,206 0,205 0,204 0,203 0,201 0,197 0,193 0,189 0,187 0,185 0,183 0,206 0,203 0,201 0,200 0,199 0,197 0,194 0,191 0,188 0,186 0,183 0,182 0,181 Version 2023-03-07 Fire damper - FDMQ 120 Page 51...
  • Page 52: Noise Data

    -24,1 -33,2 -5,2 -3,9 -4,3 -6,4 -10,1 -15,6 -22,7 -31,5 -5,5 -4,1 -5,9 -9,4 -14,6 -21,5 -5,9 -4,1 -5,6 -8,9 -13,8 -20,4 -28,8 -6,2 -4,3 -3,9 -5,3 -8,4 -13,1 -19,5 -27,6 Page 52 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 53: Material, Finishing

    Any other requirements for the design will be considered atypical and will be addressed on an individual basis. IV. INSPECTION, TESTING The damper is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjust- ■ ment. Version 2023-03-07 Fire damper - FDMQ 120 Page 53...
  • Page 54: Transportation And Storage

    The warranty for fire dampers FDMQ 120, provided by the ■ If the dampers are damaged by transport, a record must manufacturer, is completely void if actuating, closing and ■...
  • Page 55: Assembly, Attendance And Maintenance

    Protection of the damper against buckling, above all when there are big sizes of fire dampers! WRONG! Brace with wooden blocks Version 2023-03-07 Fire damper - FDMQ 120 Page 55...
  • Page 56 Change of manual control for the actuator or vice versa Damper Thermal fuse Mounting plate Manual control Sealing cover Actuator Sealing of a mounting plate Thermoelectric activation device BAT Mounting plate cover 10 Sensor sticker Page 56 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 57 Screw 5x60 mm screws into the predrilled holes FDMQ 120 Part A of VRM-Q 120 Part B of VRM-Q 120 Hexagon head screw M8x60 mm DIN 931 Screw 5x60 mm Washer M8/8,4 DIN 7349 Glue K-84 PROMAT Version 2023-03-07 Fire damper - FDMQ 120 Page 57...
  • Page 58: Entry Into Service And Revisions

    Removing the thermal fuse from the fuse holder of a manual control, checks its correct functionality. ■ The manual control is identified as M1 to M5, depending on the closing spring strength. ■ Page 58 Fire damper - FDMQ 120 Version 2023-03-07...
  • Page 59: Spare Parts

    If the thermal fuse Tf2 is interrupted (due to temperature inside the duct) , only the spare part ZBAT 72 (95/120/140) needs ■ to be replaced (acc.to the activation temperature). → see page 10 Spare parts Spare parts are supplied only on basis of an order. ■ Version 2023-03-07 Fire damper - FDMQ 120 Page 59...
  • Page 60: Product Data

    AxB EXAMPLE: FDMQ 120 800x400/375 - .40 - 800x400-damper size, /375-building lenght of a damper, .40-damper design Damper design Additional digit Manual control and thermal Manual control and thermal with a terminal switch („CLOSED“) Manual control and thermal with two terminal switches („OPEN“, „CLOSED“)
  • Page 61 The producer reserves the right for innovations of the product. For actual product information see www.mandik.com www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...