Examples of fire damper installing
The fire damper can be integrated into a solid wall construction made e.g. of normal concrete/
masonry, porous concrete with minimum thickness 100 mm or into solid ceiling construction made
e.g. of normal concrete with minimum thickness 110 mm or porous concrete with minimum
thickness 125 mm.
The fire damper can be integrated into a gypsum wall construction with fire classification EI120
or EI 90.
The fire damper can also be integrated outside the wall construction. Duct and the damper part
between the wall construction and the damper blade (labelled with BUILD IN EDGE on the
protective covering) must be protected with fire-fighting insulation.
If is square damper installed outside a construction it is necessary to use reinforcement VRM-III.
Statement of installations the fire dampers FDMB and their fire resistance Tab. 6.1.1.
Wet
Wet, battery
Wet, installation next to
wall, ceiling
Dry
Dry
Wet
Wet
Wet, battery
Dry
Wet
Dry
Mortar or gypsum
Mortar or gypsum
Mortar or gypsum and mineral wool
Installation frame and mineral wool
Stuffing box, fire protection mastic and
cement lime plate
Stuffing box and fire protection mastic
Installation frame E1, E2, R1, R2, R3,
R4
Weichschott
Battery, Installation frame
Fire resistant foam
Installation frame E4, R5
Insulation mineral wool
Installation frame E6, R6 and cement
lime plate
Insulation mineral wool
Mortar or gypsum
Mortar or gypsum
Stuffing box, fire protection mastic and
cement lime plate
Stuffing box and fire protection mastic
Installation frame E1, E2, R1, R2, R3,
R4
Weichschott
Battery Installation frame
Concrete
Concrete and Installation frame E4, R5
Insulation mineral wool
Installation frame E6, R6 and stuffing
box and fire protection mastic
Installation frame E4, R5
31
45
46
47, 48
48, 49
50
56
51
52
53
101
51
54, 104
55
103
57
58
59
67
60
61
62
64
65
63
66
60