20
A = max. 1000 mm
POSITION:
1
Fire damper FDMB with
installation frame E1, R1
2
Solid wall construction
3
Mineral stone wool min.
density 140 kg/m
4
Flange connection
20
≥ 100
≥ 100
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 mm)
or a x b = (A + 85 mm) x (2x(B + 85 mm) + 20 mm)
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(D + 141 mm) + 20 mm) x (D + 141 mm)
or. a x b = (D + 141 mm) x (2x(D + 141 mm) + 20 mm)
Gap between frame and damper body and frame and
construction must be filled by glue (PROMAT K84)
Fire damper FDMB-C - distance between dampers 104 mm
Fire damper FDMB-K - distance between dampers 160 mm
Flange to flange connection - Up to four dampers can be installed
20
41
≥ 100
20
≥ 100
It is possible to use
corresponding number of
holes and screws
Number
Number