Mandik FDMB Manual page 11

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

Design .41 or .51 with actuating mechanism can be complemented with smoke detector
MHG 231. The voltage can be AC 230 V or AC/DC 24 V. Design with voltage AC 230 V is
equpped with Communication and supply device BKN 230-24-MA and with actuating mechanism
BF 24-T (BFL 24-T, BFN 24-T).
The smoke detector is activated when smoke spreads in air duct system. Deactivation of smoke
detector is provided by interruption of supply voltage for min. 2s.
Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches.
Nominal voltage
Voltage range
Power Consumption Socket
(without actuating mechanism)
Degree of protection
Ambient temperature
Non-operating temperature
Connection - net
- motor
- communication and supply device
BKN 230-24-MA
AC/DC 24 V
AC 18 ... 28 V
DC 24 ... 30 V
max. 50mA
- 25 °C ... + 70 °C
- 5 °C ... + 40 °C
Cabel 1m, connected to terminal XT1
Screw terminals on the terminal block XT2
Screw terminals on the terminal block XT1 a XT2
10
IP 40