Download Print this page

Mandik FDMB Manual page 51

Fire dampers
Hide thumbs Also See for FDMB:

Advertisement

20
20
A = max. 1000 mm
POSITION:
1 Fire damper FDMB
with installation frame E1, R2
2 Solid ceiling construction
3 Mineral stone wool min. density
140 kg/m
4 Flange connection
150*
150*
* min. 110 - Concrete/ min. 125 - Aerated concrete
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 mm)
or a x b = (A + 85 mm) x (2x(B + 85 mm) + 20 mm)
Fire damper FDMB-C - installation opening dimensions
a x b = (2x(D + 141 mm) + 20 mm) x (D + 141 mm)
or a x b = (D + 141 mm) x (2x(D + 141 mm) + 20 mm)
Gap between frame and damper body and frame and construction
must be filled by glue (PROMAT K84)
Fire damper FDMB-C - distance between dampers 104 mm
Fire damper FDMB-K - distance between dampers 160 mm
Flange to flange connection - Up to four dampers can be installed
50
20
20
150*
It is possible to use
corresponding number of
holes and screws
Number
Dimensions
A1,B1,D1 ≤ 400
400 < A1,B1,D1 ≤ 800
800 < A1,D1 ≤ 1260
1260 < A1,D1 ≤ 1600
1600 < A1 ≤ 2000
150*
Number
ZB1
ZH1
1
1
2
2
3
3
4
4
5
5