Installation frame R5 is suitable for:
● Instalaci on solid wall/ceiling construction
● Instalaci outside solid ceiling constructions with concrete
On the inside is installation frame equipped by intumescent sealing. It enlarges its capacity and air
proofs the gap between installation frame and damper body.
● Gypsum wall construction has to be installed according manufacture requirements.
● Installation frame:
● Fasteners:
● d = (D + 10 mm)
● d = (D + 100 mm) installation with concrete
cement lime plates and galvanized plate
galvanized plate
150*
max. 750
150*
POSITION:
1
2
3
4
79
max. 100
* min. 110 - Concrete
min. 125 - Aerated concrete
Fire damper FDMB with installation frame R5
Fitting with threaded rods or steel bracket
Concrete B20
Rebar