Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault
Internal SSW fault
User set fault
Kernel overload
Parameter system
FBA A parameter
conflict
FBA B parameter
conflict
Text data overflow
Text 32-bit table
overflow
Text 64-bit table
overflow
Text file overflow
Option module
comm loss
Panel port
communication
Programmable fault: 49.05
Communication loss action
Ext I/O comm loss
13-14 Troubleshooting
Fault #
Cause
64B1
Internal fault.
64B2
Loading of user parameter
set failed because
• requested set does
not exist
• set is not compatible
with control program
• drive was switched off
during loading.
64E1
Operating system error.
6581
Parameter load or save
failed.
65A1
The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
65A2
The drive does not have a
functionality requested by
PLC, or requested
functionality has not been
activated.
6881
Internal fault.
6882
Internal fault.
6883
Internal fault.
6885
Internal fault.
7080
Communication between
drive and an option
module is lost.
7081
Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
7082
The I/O extension module
types specified by
parameters do not
match the detected
configuration.
00 0001
Communication with
module failed.
00 0002
Module not found.
00 0003
Configuration of module
failed.
00 0004
Configuration of module
failed.
What to do
Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Ensure that a valid user parameter set exists. Reload if
uncertain.
Reboot the control unit (using parameter 96.08 Control
board boot) or by cycling power. If the problem persists,
contact your local ABB representative.
Try forcing a save using parameter 96.07 Parameter save
manually. Retry.
Check PLC programming.
Check settings of parameter groups 50 Fieldbus adapter
(FBA) and 51 FBA A settings.
Check PLC programming.
Check settings of parameter groups 50 Fieldbus adapter
(FBA) and 54 FBA B settings.
Reset the fault. Contact your local ABB representative if
the fault persists.
Reset the fault. Contact your local ABB representative if
the fault persists.
Reset the fault. Contact your local ABB representative if
the fault persists.
Reset the fault. Contact your local ABB representative if
the fault persists.
Check that all option modules are properly seated in their
slots.
Check that all option modules or slot connectors are
not damaged. To pinpoint the problem, try installing the
modules into different slots one at a time.
Check PC tool or control panel connection.
Check control panel connector. Disconnect and reconnect
the control panel.
Check the event log for an auxiliary code (format XXYY
YYYY). "XX" specifies the number of the I/O extension
module (01: parameter group 14 I/O extension module
1, 02: 15 I/O extension module 2, 03: 16 I/O extension
module 3). "YY YYYY" indicates the problem (see actions
for each code below).
Check that the module is properly seated in its slot.
Check that the module and the slot connector is not
damaged. Try installing the module into another slot.
Check the type and location settings of the modules
(parameters 14.01/14.02, 15.01/15.02 or 16.01/16.02).
Check that the module is properly seated in its slot.
Check that the module and the slot connector is not
damaged. Try installing the module into another slot.
3AXD50000011888