Table 13-1 Warning Messages (Alphabetical by Keypad Text)
Warning
Mechanical brake
opening not allowed
Programmable warning:
44.17 Brake fault function
FIO-11 AI
parametrization
Extension I/O
configuration failure
Motor speed
feedback
Programmable warning:
90.45 Motor feedback fault
FBA A
communication
Programmable warning:
50.02 FBA A comm loss func
FBA B
communication
Programmable warning:
50.32 FBA B comm loss func
DDCS controller
comm loss
Programmable warning:
60.59 DDCS controller
comm loss function
13-6 Troubleshooting
Fault #
Cause
A7A5
Open conditions of
mechanical brake
cannot be fulfilled (for
example, brake has been
prevented from opening
by parameter 44.11 Keep
brake closed).
A7AA
The hardware current/
voltage setting of an
analog input (on an
I/O extension module)
does not correspond to
parameter settings.
A7AB
The I/O extension module
types and locations
specified by parameters
do not match the detected
configuration.
A7B0
No motor speed feedback
is received.
0001
Motor gear definition
invalid or outside limits.
0002
Encoder not configured.
0003
Encoder stopped working. Check encoder status.
0004
Encoder drift detected.
A7C1
Cyclical communication
between drive and
fieldbus adapter module
A or between PLC and
fieldbus adapter
module A is lost.
A7C2
Cyclical communication
between drive and
fieldbus adapter module
B or between PLC and
fieldbus adapter
module B is lost.
A7CA
DDCS (fiber optic)
communication between
drive and external
controller is lost.
What to do
Check mechanical brake settings in parameter group 44
Mechanical brake control (especially 44.11 Keep brake
closed).
Check that acknowledgement signal (if used) matches
actual status of brake.
Check the event log for an auxiliary code (format 0000
XXYY). "XX" specifies the number of the I/O extension
module (01: parameter group 14 I/O extension module
1, 02: 15 I/O extension module 2, 03: 16 I/O extension
module 3). "YY" specifies the analog input on the module.
For example, in case of I/O extension module 1, analog
input AI1 (auxiliary code 0000 0101), the hardware
current/voltage setting on the module is shown by
parameter 14.29. The corresponding parameter setting is
14.30. Adjust either the hardware setting on the module
or the parameter to solve the mismatch.
Note: Control board reboot (either by cycling the power or
through parameter 96.08 Control board boot) is required
to validate any changes in the hardware settings.
Check the event log for an auxiliary code. The code
indicates which I/O extension module is affected.
Check the type and location settings of the modules
(parameters 14.01, 14.02, 15.01, 15.02, 16.01 and 16.02).
Check that the modules are properly installed.
Check the event log for an auxiliary code (format XXYY
ZZZZ). "XX" specifies the number of the encoder interface
module (01: 91.11/91.12, 02: 91.13/91.14), "YY" specifies
the encoder (01: 92 Encoder 1 configuration, 02: 93
Encoder 2 configuration). "ZZZZ" indicates the problem
(see actions for each code below).
Check motor gear settings (90.43 and 90.44).
Check encoder settings (92 Encoder 1 configuration or 93
Encoder 2 configuration).
Use parameter 91.10 Encoder parameter refresh) to
validate any changes in the settings.
Check for slippage between encoder and motor.
Check status of fieldbus communication. See user
documentation of fieldbus interface.
Check settings of parameter groups 50 Fieldbus adapter
(FBA), 51 FBA A settings, 52 FBA A data in and 53 FBA A
data out.
Check cable connections.
Check if communication master is able to communicate.
Check status of fieldbus communication. See user
documentation of fieldbus interface.
Check settings of parameter group 50 Fieldbus adapter
(FBA).
Check cable connections.
Check if communication master is able to communicate.
Check status of controller. See user documentation of
controller.
Check settings of parameter group 60 DDCS
communication.
Check cable connections. If necessary, replace cables.
3AXD50000011888

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01-24a3-2+n5350Acs880-01-031a-2+n5350Acs880-01-046a-2+n5350Acs880-01-061a-2+n5350Acs880-01-075a-2+n5350Acs880-01-087a-2+n5350 ... Show all