Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault
ID run
13-18 Troubleshooting
Fault #
Cause
FF61
Motor ID run was not
completed successfully.
0001
Maximum current limit too
low.
0002
Maximum speed limit or
calculated field weakening
point too low.
0003
Maximum torque limit too
low.
0004
Current measurement
calibration did not finish
within reasonable time.
0005 - 0008
Internal error.
0009
(Asynchronous motors
only) Acceleration did not
finish within reasonable
time.
000A
(Asynchronous motors
only) Deceleration did not
finish within reasonable
time.
000B
(Asynchronous motors
only) Speed dropped to
zero during ID run.
000C
(Permanent magnet
motors only) First
acceleration did not
finish within reasonable
time.
000D
(Permanent magnet
motors only) Second
acceleration did
not finish within
reasonable
time.
000E - 0010
Internal error.
What to do
Check the nominal motor values in parameter group 99
Motor data.
Check that no external control system is connected to the
drive.
Cycle the power to the drive (and its control unit, if
powered separately).
Check that the motor shaft is not locked.
Check the event log for an auxiliary code. The second
number of the code indicates the problem (see actions for
each code below).
Check settings of parameters 99.06 Motor nominal current
and 30.17 Maximum current. Make sure that 30.17 >
99.06.
Check that the drive is dimensioned correctly according to
the motor.
Check settings of parameters
• 30.11 Minimum speed
• 30.12 Maximum speed
• 99.07 Motor nominal voltage
• 99.08 Motor nominal frequency
• 99.09 Motor nominal speed.
Make sure that
• 30.12 > (0.55 × 99.09) > (0.50 × synchronous speed)
• 30.11 < 0, and
• supply voltage > (0.66 × 99.07).
Check settings of parameter 99.12 Motor nominal torque,
and the torque limits in group 30 Limits.
Make sure that the maximum torque limit in force is
greater than 100%.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
3AXD50000011888