ABB ACS880+N5350 User Manual page 138

Cooling tower drives
Table of Contents

Advertisement

Parameter (Number)
Block Title
STANDARD AI
AO2 SOURCE MIN (13.27)
(Continued)
AO2 SOURCE MAX (13.28)
AO2 OUT AT AO2 SRC MIN
(13.29)
AO2 OUT AT AO2 SRC MAX
(13.30)
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
Default: 0.0
Range: -32768.0 to +32767.0
Defines the real minimum value of the signal (selected by parameter
13.22 AO2 source) that corresponds to the minimum required AO2
output value (defined by parameter 13.29 AO2 out at AO2 src min).
I
AO1
13.20
13.19
Programming 13.27 as the maximum value and 13.28 as the minimum
value inverts the output.
I
AO1
13.20
13.19
Default: 100.0
Range: -32768.0 to +32767.0
Defines the real maximum value of the signal (selected by parameter
13.22 AO2 source) that corresponds to the maximum required AO2
output value (defined by parameter 13.30 AO2 out at AO2 src max).
See parameter 13.27 AO2 source min.
Default: 0.000mA
Range: 0.000 - 22.000mA
Defines the minimum output value for analog output AO2. See also
drawing at parameter 13.27 AO2 source min.
Default: 20.000mA
Range: 0.000 - 22.000mA
Defines the maximum output value for analog output AO2. See also
drawing at parameter 13.27 AO2 source min.
Descriptions
(mA)
13.17
13.18
(mA)
13.18
13.17
Startup Assistant & Parameters 12-59
Signal (real)
selected by
13.12
Signal (real)
selected by
13.12