ABB ACS880+N5350 User Manual page 130

Cooling tower drives
Table of Contents

Advertisement

Parameter (Number)
Block Title
STANDARD DIO,
DIO1 ON DELAY (11.07)
FI, FO
(Continued)
DIO1 OFF DELAY (11.08)
DIO2 FUNCTION (11.09)
DIO2 OUTPUT SOURCE (11.10) Default: Running (7)
DIO2 ON DELAY (11.11)
DIO2 OFF DELAY (11.12)
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO1 (when used
as a digital output or digital input).
*Delayed DIO status
t
= 11.07 DIO1 ON delay
On
t
= 11.08 DIO1 OFF delay
Off
*Electrical status of digital input. Indicatedc by 11.01 DIO status.
Default: 0.0 s
**Indicated by 11.02 DIO delayed status.
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input/output DIO1 (when used
as a digital output or digital input). See parameter 11.07 DIO1 ON
delay.
Default: Output (0)
Range: 0 - 2
Output (0) DIO2 is used as a digital output
Input (1) DIO2 is used as a digital input
Frequency (2) DIO2 is used as a frequency input
Selects whether DIO2 is used as a digital output or input, or a
frequency output.
Range: 0 - 44, Other
Selects a drive signal to be connected to digital input/output DIO2
when parameter 11.09 DIO2 function is set to Output.
For the available selections, see parameter 11.06 DIO1 output source.
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO2 (when used
as a digital output or digital input).
*Delayed DIO status
t
= 11.11 DIO2 ON delay
On
t
= 11.12 DIO2 OFF delay
Off
*Electrical status of digital input. Indicatedc by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input/output DIO2 (when used
as a digital output or digital input). See parameter 11.11 DIO2 ON
delay.
Descriptions
*DIO status
t
t
On
Off
*DIO status
t
t
On
Off
Startup Assistant & Parameters 12-51
1
0
1
0
Time
t
t
On
Off
1
0
1
0
Time
t
t
On
Off

Advertisement