ABB ACS880+N5350 User Manual page 163

Cooling tower drives
Table of Contents

Advertisement

Parameter (Number)
Block Title
EMBEDDED
DATA I/O 1 (58.101)
FIELDBUS
(Continued)
DATA I/O 2 (58.102)
DATA I/O 3 (58.103)
12-84 Startup Assistant & Parameters
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
0 (None) None
1 (CW 16bit) Control Word (16 bits)
2 (Ref1 16bit) Reference REF1 (16 bits)
3 (Ref2 16bit) Reference REF2 (16 bits)
4 (SW 16bit) Status Word (16 bits)
5 (Act1 16bit) Actual value ACT1 (16 bits)
6 (Act2 16bit) Actual value ACT2 (16 bits)
11 (CW 32bit) Control Word (32 bits)
12 (Ref1 32bit) Reference REF1 (32 bits)
13 (Ref2 32bit) Reference REF2 (32 bits)
14 (SW 32bit) Status Word (32 bits)
15 (Act1 32bit) Actual value ACT1 (32 bits)
16 (Act2 32bit) Actual value ACT2 (32 bits)
21 (CW2 16bit)
24 (SW2 16bit)
31 (RO/DIO control word) Parameter 10.99 RO/DIO control word
32 (AO1 data storage) Parameter 13.91 AO1 data storage
33 (AO2 data storage) Parameter 13.92 AO2 data storage
40 (Feedback data storage) Parameter 40.91 Feedback data storage
41 (Setpoint data storage) Parameter 40.92 Setpoint data storage
Other (-) Source selection (see Terms and abbreviations)
Default: 1 (CW 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Control Word 2 (16 bits)
When a 32-bit control word is used, this setting means the mostsignificant
16 bits
Status Word 2 (16 bits).
When a 32-bit control word is used, this setting means the mostsignificant
16 bits
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400001.
The master defines the type of the data (input or output). The value is
transmitted in a Modbus frame consisting of two 16-bit words. If the
value is 16-bit, it is transmitted in the LSW (least significant word). If
the value is 32-bit, the subsequent parameter is also reserved for it
and must be set to None.
Default: 2 (Ref1 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400002.
For the selections, see parameter 58.101 Data I/O 1.
Default: 3 (Ref2 16bit)
Range: 0 - 6, 11 - 16, 21, 24, 31 - 33, 40, 41
Defines the address in the drive which the Modbus master accesses
when it reads from or writes to register address 400003.
For the selections, see parameter 58.101 Data I/O 1.
Descriptions
3AXD50000011888