Group 52 FBA A Data In (PLC Input Data)
(Note: that first three words back to PLC are pre-defined or already mapped for you.)
Main Status Word (MSW)
Actual Value 1
Actual Value 2
52.01 FBA A Data In1 = Parameter 1.07[16]
52.02 FBA A Data In2 = Parameter 1.11[16]
52.03 FBA A Data In3 = Parameter 1.14[16]
52.04 FBA A Data In1...
52.10 FBA A Data In10
(Note: the first three words sent to the drive are pre-defined or already mapped for you.)
Main Control Word (MCW)
Speed Reference 1
Reference 2
53.01 FBA A Data Out1 = Parameter 23.14[16]
53.04 FBA A Data Out1...
53.10 FBA A Data Out10
Last step after changing any fieldbus related parameters in Groups 50-53:
51.27 FBA A Par Refresh
ACS880 CTDD Drive on EtherNet/IP FENA-21 or FEIP-21 with Studio 5000 Logix Designer® or RSLogix® 5000
1.
Open Studio 5000 Logix Designer® or RSLogix® 5000 and open a new project.
2.
Right click on the Ethernet module within the Controller Organizer window.
G-2 Ethernet/IP Setup
See status word bit description below
Speed (1=1rpm)
Torque (% of motor nominal x 100)
Motor Current (1=1Amp)
DC Bus Voltage x 10
Actual motor power in HP x 10
These additional data words could be used to read other parameters
from the drive.
These additional data words could be used to read other parameters
from the drive.
See control word bit description below.
Scaling is 1=1rpm
Not used in ACS880 CTDD
Accel Time 2 (optional) These additional data words could be used to
write to other parameters within the drive.
For example, writing a value of 300 here would set par 23.12 Accel
Time 1 to 30 seconds.
Up to 10 additional parameters can be mapped here for cyclic
updating.
Up to 10 additional parameters can be mapped here for cyclic
updating.
Refresh Reboots fieldbus card so changes will take effect (or the drive
power can be cycled).