Motor ID Run
The drive is now ready to run the motor identification
routine (ID run). The motor is injected with DC
current.
Use the
key to select Standstill ID run and then
press
(next).
Note: On initial startup, an ID run must be performed
and Next will not advance to next step.
Motor ID Run
No command rotation is given, however with a
permanent magnet motor the shaft could rotate up
to half a revolution.
You must press Local Keypad START to activate ID
Run.
Note: ID Run requires Local control, press
if the Keypad does not indicated
Loc/Rem
local control is active.
Next is not visible until ID run is performed
once.
12-6 Startup Assistant & Parameters
Table 12-1 Initial Start-up / Motor Data and ID Run
Local
CTDD
ID run?
None
Standstill ID run
Back
00:00
Local
CTDD
ID run?
None
Standstill ID run
Back
00:00
Local
CTDD
Press Start for ID run
When you press Start, the motor is
injected with DC
Current for about 1 minute, and may
Rotate up to half a
Revolution. After the ID run the drive
stops.
Back
00:00
50.0 rpm
Next
50.0 rpm
Next
50.0 rpm
Next
3AXD50000011888

Advertisement

Table of Contents