Parameter (Number)
Block Title
FIELDBUS
Parameters 50 - 56 are for FIELDBUS ONLY and are adapter module-specific. For more
information, see the documentation of the fieldbus adapter module. Note that not all of these
ADAPTER
parameters are necessarily in use.
EMBEDDED
Configuration of the embedded fieldbus (EFB) interface. See also chapter Fieldbus control through the
FIELDBUS
embedded fieldbus interface (EFB).
PROTOCOL ENABLE (58.01)
PROTOCOL ID (58.02)
NODE ADDRESS (58.03)
BAUD ADDRESS (58.04)
PARITY (58.05)
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
Default: 0 (None)
Range: 0, 1
None (communication disabled)
0 (None)
Embedded fieldbus interface is enabled and uses the Modbus RTU
1 (Modbus RTU)
protocol
Enables/disables the embedded fieldbus interface and selects the
protocol to use.
Note: When the embedded fieldbus interface is enabled, the drive-to-
Default: Read Only
Range: -
Displays the protocol ID and revision.
This parameter is read-only.
Default: 1
Range: 0 - 255
Defines the node address of the drive on the fieldbus link.
Values 1 - 247 are allowable. Two devices with the same address are
not allowed on-line.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Default: 3 (19.2 kbps)
Range: 2 - 7
2 (9.6 kbps)
9.6 kbit/s
3 (19.2 kbps) 19.2 kbit/s
4 (38.4 kbps) 38.4 kbit/s
5 (57.6 kbps) 57.6 kbit/s
6 (76.8 kbps) 76.8 kbit/s
7 (115.2 kbps) 115.2 kbit/s
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Default: 2 (8 EVEN 1)
Range: 0 - 3
0 (8 NONE 1)
Eight data bits, no parity bit, one stop bit
1 (8 NONE 2) Eight data bits, no parity bit, two stop bits
2 (8 EVEN 1) Eight data bits, even parity bit, one stop bit
3 (8 ODD 1) Eight data bits, odd parity bit, one stop bit
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Descriptions
drive link functionality is automatically disabled.
Startup Assistant & Parameters 12-77