ABB ACS880+N5350 User Manual page 229

Cooling tower drives
Table of Contents

Advertisement

51.08 IP Address
51.09 Subnet CIDR = 24
51.10 GW Address
51.11 GW Address
51.12 GW Address
51.13 GW Address
51.20 Timeout Time = 30
51.21 Timeout Mode = Control RW
Group 52 FBA A Data In (PLC Input Data)
(Note: that first three words back to PLC are pre-defined or already mapped for you.)
Status Word (SW)
Actual Value 1 =
Actual Value 2 =
52.01 FBA A Data In1 = Parameter 1.07
52.02 FBA A Data In2 = Parameter 1.11
52.03 FBA A Data In3 = Parameter 1.14
...
52.12 FBA A Data In12
Group 53 FBA A Data Out (PLC Output Data)
(Note: the first three words sent to the drive are pre-defined or already mapped for you.)
Control Word (CW)
Ref 1
Ref 2
53.01 FBA A Data Out1 = Parameter 23.12
53.02 FBA A Data Out 1...
53.12 FBA A Data Out12
Last step after changing any fieldbus related pars in Groups 50-53:
51.27 FBA A Par Refresh = Refresh
E-2 ModbusTCP Setup
ex. 10
Shorthand for 255.255.255.0
Leave at default (zero) if not used
Leave at default (zero) if not used
Leave at default (zero) if not used
Leave at default (zero) if not used
3 sec (value put here is multiplied times 100ms)
Monitors updating of CW and REF1
Register 40051. See status word bit description below
Register 40052. Speed (1=1rpm)
Register 40053. Torque (% of motor nominal x 100)
Register 40054. Motor Current (1=1Amp)
Register 40055. DC Bus Voltage x 10
Register 40056. Actual motor power in HP x 10
...
Register 40065. These additional data words could be used to read
other parameters from the drive.
Register 40001. See control word bit description below
Register 40002. Scaling is 1=1rpm
Register 40003. Not used.
Register 40004. (optional) These additional data words could be used
to write to other parameters.
For example, writing a value of 300 here would set par 23.12 Accel
Time 1 to 30 seconds.
Register 40015. Up to 12 additional parameters can be mapped here
for cyclic updating
Register 40015. Up to 12 additional parameters can be mapped here
for cyclic updating
Reboots fieldbus card so changes can take effect
3AXD50000011888