Cooling tower drives
Table of Contents

Advertisement

5.
Program the following information below. The ACS880 CTDD Drive only supports the 16 Bit Transparent assembly
instances displayed below. This example will use 16 Bit transparent Profile Assembly Instances 112 and 162. The
following table will display Input and Output Assembly Instances and PLC I/O Memory size.
Input Assembly Instances
Reference FENA-01/-11/-21 EtherNet Adapter Module User's Manual 3AUA0000093568 section "Communication"
for more information on Input/Output Assembly Instances and reference FEIP-21 Ethernet IP User's Manual
3AXD50000158621.
6.
Enter the following information. The example shown is using the B16 Bit Transparent Profile Assembly Instances
112 and 162. The PLC will transmit and receive 13 words of information.
a. Enter the name that will be given to the Cooling Tower Drive
b. Change Comm Format to Data - INT (16Bits)
c. Enter the IP Address of the Ethernet option card
d. Enter Input and Output Assembly Instances numbers.
e. Enter Input and Output Assembly Instances numbers.
f. Enter configuration instance as 1 and size as 0.
7.
Click Finish.
G-4 Ethernet/IP Setup
Output Assembly Instances PLC Word Settings
61
62
161
162
11
2
12
3
111
12
112
13
A
B
C
D
E
F
3AXD50000011888