Parameter (Number)
Block Title
EMBEDDED
ADDRESSING MODE (58.33)
FIELDBUS
(Continued)
WORD ORDER (58.34)
EFB COMM SUPERVISION
FORCE (58.36)
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
Default: 0 (Mode 0)
Range: 0 - 2
16-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 400000 + 100 × parameter group + parameter
index. For example, parameter 22.80 would be mapped to register
400000 + 2200 + 80 = 402280.
0 (Mode 0)
32-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 420000 + 200 × parameter group + 2 × parameter
index. For example, parameter 22.80 would be mapped to register
420000 + 4400 + 160 = 424560.
16-bit values (groups 1 - 255, indexes 1 - 255):
Register address = 400000 + 256 × parameter group + parameter
1 ( Mode 1)
index. For example, parameter 22.80 would be mapped to register
400000 + 5632 + 80 = 405712.
32-bit values (groups 1 - 127, indexes 1 - 255):
Register address = 400000 + 512 × parameter group + 2 × parameter
2 ( Mode 2)
index. For example, parameter 22.80 would be mapped to register
400000 + 11264 + 160 = 411424.
Defines the mapping between parameters and holding registers in the
400101 - 465535 Modbus register range.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Default: 1 (LO-HI)
Range: 0, 1
The first register contains the high order word, the second contains
0 (HI-LO)
the low order word.
The first register contains the low order word, the second contains the
1 (LO-HI)
high order word.
Selects in which order 16-bit registers of 32-bit parameters are
transferred.
For each register, the first byte contains the high order byte and the
second byte contains the low order byte.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
Default: 0000b
Range: 0000b - 0111b
Activates fieldbus communication monitoring separately for each
control location (see section Local control vs. external control).
The parameter is primarily intended for monitoring the communication
with EFB when it is connected to the application program and not
selected as a control source by drive parameters.
Bit
0
1
2
3-15
Descriptions
Name
1 = Communication monitoring active
Ext 1
when Ext 1 is being used
1 = Communication monitoring active
Ext 2
when Ext 2 is being used
1 = Communication monitoring active
Local
when local control is being used
Reserved
Startup Assistant & Parameters 12-83