Parameter (Number)
Block Title
STANDARD DI, RO
RO2 ON DELAY (10.028)
(Continued)
RO3 OFF DELAY (10.32)
DI FILTER TIME (10.51)
RO/DIO CONTROL WORD
(10.99)
STANDARD DIO,
Configuration of digital input/outputs and frequency inputs/outputs.
FI, FO
DIO STATUS (11.01)
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Selection (Value)
Default: 0.0 s (95.20 b3)
Range: 0.0 to 3000.0 s
Defines the activation delay for relay output RO3.
Status of selected
t
= 10.31 RO3 ON delay
On
t
= 10.32 RO3 OFF delay
Off
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for relay output RO3. See parameter
10.31 RO3 ON delay.
Default: 10.0 ms
Range: 0.3 - 100.0 ms
Defines a filtering time for parameter 10.01 DI status.
Default: 0000h
Range: 0000h - FFFFh
Storage parameter for controlling the relay outputs and digital input/
outputs eg. through the embedded fieldbus interface.
To control the relay outputs (RO) and the digital input/outputs (DIO)
of the drive, send a control word with the bit assignments shown
below as Modbus I/O data. Set the target selection parameter of that
particular data (58.101 - 58.124) to RO/DIO control word. In the source
selection parameter of the desired output, select the appropriate bit of
this word.
Bit
0
1
2
3-7
8
9
10-15 Reserved
Default: Read Only
Range: 0000b - 0011b
Displays the status of digital input/outputs DIO2 and DIO1. The
activation/deactivation delays (if any are specified) are ignored. A
filtering time (for input mode) can be defined by parameter 10.51 DI
filter time. Example: 0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
Descriptions
source
RO status
t
t
On
Off
Name
Description
RO1
Source bits for relay outputs RO1 - RO3 (see
RO2
parameters 10.24, 10.27 and 10.30).
RO3
Reserved
DIO1
Source bits for digital input/outputs DIO1 -
DIO3 (see parameters 11.06 and 11.10).
DIO2
Startup Assistant & Parameters 12-49
1
0
1
0
Time
t
t
On
Off