Default I/O Connections; Predefined Disturbance Recorder Connections - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
3.4.2.1
3.4.2.2
REB611
Application Manual

Default I/O connections

Table 11:
Default connections for binary inputs
Binary input
Description
X120-BI1
-
X120-BI2
Circuit breaker closed position indication
X120-BI3
Circuit breaker open position indication
X120-BI4
Circuit breaker close enable status
Table 12:
Default connections for binary outputs
Binary input
Description
X100-PO1
Close circuit breaker
X100-PO2
Circuit breaker failure protection trip to upstream breaker
X100-PO3
Open circuit breaker/trip coil 1
X100-PO4
Open trip coil 2
X100-SO1
General start indication
X100-SO2
General operate indication
Table 13:
Default connections for LEDs
LED
Description
1
High-impedance differential protection stage 1 operate
2
High-impedance differential protection stage 2 operate
3
High-impedance differential protection stage 3 operate
4
High-impedance differential protection start
5
Dedicated phase-segregated supervision function alarm
6
Disturbance recorder triggered
7
Trip circuit supervision alarm
8
Circuit-breaker failure operate

Predefined disturbance recorder connections

Table 14:
Predefined analog channel setup
Channel
Description
1
IL1
2
IL2
3
IL3
4
Io
REB611 standardized configuration
Section 3
Connector pins
X120:1-2
X120:3,2
X120:4,2
X120:5-6
Connector pins
X100:6-7
X100:8-9
X100:15-19
X100:20-24
X100:10-12
X100:13-15
33