Functional Diagrams For Protection - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MRS758272 B
3.3.3.1
REG615
Application Manual
fixed Boolean signals TRUE and FALSE which can be used according to the
application needs.

Functional diagrams for protection

The functional diagrams describe the relay protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection. Three
of them include directional functionality DPHxPDOC. Three-phase non-directional
overcurrent protection, instantaneous stage, PHIPTOC1 can be blocked by activation
of inrush protection.
INRPHAR1_BLK2H
GUID-3B337137-069C-45D9-8CA0-3D712B38D585 V2 EN
Figure 15:
Overcurrent protection function
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC2_OPERATE
GUID-74C92AEB-2DBA-411B-945B-2C494DAB111E V2 EN
Figure 16:
Directional overcurrent protection function
The output BLK2H of three-phase inrush detector INRPHAR1 enables either blocking
the function or multiplying the active settings for any of the available overcurrent or
earth-fault function blocks. In the configuration, INRPHAR1 blocks the non-
directional instantaneous stage.
REG615 standard configurations
PHIPTOC1(3I>>>(
BLOCK
OPERATE
ENA_MULT
START
DPHHPDOC1(3I>>-
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC1(3I>->
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
DPHLPDOC2(3I>->
BLOCK
OPERATE
ENA_MULT
START
NON_DIR
OR6
B1
O
B2
B3
B4
B5
B6
Section 3
PHIPTOC1_OPERATE
PHIPTOC1_START
DPHHPDOC1_OPERATE
DPHHPDOC1_START
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHLPDOC2_OPERATE
DPHLPDOC2_START
DPHxPDOC_OPERATE
43