Can Communication (Sgc 120 Only); About The Can Communication Protocol; Can Communication Structure - Deif SGC 120 User Manual

Single genset controller
Hide thumbs Also See for SGC 120:
Table of Contents

Advertisement

12. CAN communication (SGC 120 only)

12.1 About the CAN communication protocol

SGC 120 supports a CAN based protocol, which is used to read measurement values, status of alarms and derived calculations
(such as cumulative power), as well as to send mode change and start/stop commands to the controller.
Connection details:
Baud rate used for communication is 250 kbps
ID of the controller is fixed to 0x01
ID scheme for CAN communication is Standard ID (not extended ID)
Packet size used for communication is 8 bytes

12.2 CAN communication structure

The controller continuously broadcasts measurement values, status of alarms and commands, and derived calculations. Additionally,
a set of commands can be sent to the controller. Response to the commands is a part of the data that is broadcast.
Communication structure, page 0
Register offset
Value
0
Protocol revision
1
Generator L1-N voltage
2
Generator L2-N voltage
Communication structure, page 1
Register offset
Value
3
Generator L2-L3 voltage
4
Generator L1-L2 voltage
5
Generator L3-N voltage
Communication structure, page 2
Register offset
Value
6
Generator L3-L1 voltage
7
Generator L2 frequency
8
Generator L1 frequency
Communication structure, page 3
Register offset
Value
9
Generator power factor L2
10
Generator L3 frequency
11
Generator power factor L1
USER MANUAL 4189341226A UK
Scale factor
Unit
-
-
1
V
1
V
Scale factor
Unit
1
V
1
V
1
V
Scale factor
Unit
1
V
1
Hz
1
Hz
Scale factor
Unit
1
-
1
Hz
1
-
Bits/Sign
Unsigned
Unsigned
Unsigned
Bits/Sign
Unsigned
Unsigned
Unsigned
Bits/Sign
Unsigned
Unsigned
Unsigned
Bits/Sign
Unsigned
Unsigned
Unsigned