Table 6.23
Speed Monitoring (SPEED MONITOR)
Level 2
Engine Speed Sense Source
(SPEED SENSE SOURCE)
Flywheel Teeth (Magnetic Pickup)
W-Point Frequency@ 1500
Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
Under-speed Threshold
(UNDER SPEED THRESH)
Under-speed Delay
(UNDER SPEED DELAY)
Over-speed Threshold
(OVER SPEED THRESH)
Over-speed Delay
(OVER SPEED DELAY)
Gross Over-speed Threshold
(GROSS OS THRESHOLD)
Table 6.24
Battery Monitoring (BATTERY MONITOR)
Level 2
Low Battery Voltage Action
(LOW VOLT ACTION)
Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
Low Battery Voltage Delay
(LOW VOLT DELAY)
High Battery Voltage Action
(HIGH VOLT ACTION)
High Battery Voltage Threshold
(HIGH VOLT THRESHOLD)
High Battery Voltage Delay
(HIGH VOLT DELAY)
Table 6.25
Charging Alternator Monitoring (CHARGE ALT MON)
Level 2
Charging Alternator Fail Action
(FAIL ACTION)
USER MANUAL 4189341226A UK
Range
Alternator frequency
Magnetic Pickup
W-Point Frequency
1 to 300
0 to 500
Enable
Disable
0 to 3600 RPM
1 to 60 s
700 to 4000 RPM
1 to 20 s
100 to 200 %
Range
None
Notification
Warning
Electrical Trip
Shutdown
8.0 to 31.0 V
5 to 1800 s
None
Notification
Warning
Electrical Trip
Shutdown
9.0 to 32.0 V
5 to 1800 s
Range
None
Notification
Warning
Electrical Trip
Page 33 of 72