Advertisement

Level 2
Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
Over-voltage Shutdown Threshold
(OV SHUTDOWN THRESH)
Over-voltage Warning
(OVER VOLT WARNING)
Over-voltage Warning Threshold
(OV WARNING THRESHOLD)
Table 6.16
Frequency Monitoring (FREQ MONITOR)
Level 2
Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
Under-frequency Shutdown Threshold
(UF SHUTDOWN THRESH)
Under-frequency Warning Enable
(UNDER FREQ WARNING)
Under-frequency Warning Threshold
(UF WARNING THRESHOLD)
Over-frequency Shutdown Enable
(OVER FREQ SHUTDOWN)
Over-frequency Shutdown Threshold
(OF SHUTDOWN THRESH)
Over-frequency Warning Enable
(OVER FREQ WARNING)
Over-frequency Warning Threshold
(OF WARNING THRESHOLD)
Table 6.17
Current Monitoring (CURRENT MONITOR)
Level 2
CT Ratio
(LOAD CT RATIO)
Over-current Action
(OVER CURR ACTION)
Over-current Threshold
(OVER CURR THRESHOLD)
Over-current Delay
(OVER CURR DELAY)
CT Correction Factor
CT Location
(CT LOCATION)
USER MANUAL 4189341226A UK
Range
Enable
Disable
105 to 350 V phase-neutral
Enable
Disable
100 to 345 V phase-neutral
Range
Enable
Disable
10.0 to 59.0 Hz
Enable
Disable
11.0 to 60.0 Hz
Enable
Disable
26.0 to 75.0 Hz
Enable
Disable
25.0 to 74.0 Hz
Range
0 to 8000 / 5
None
Notification
Warning
Electrical Trip
Shutdown
5 to 10000 A
1 to 600 s
0.900 to 1.100
On Alt Output Cable
On Load Cable