Figure 4.2
SGC 121 typical wiring
P1
L1
s1
L2
G
L3
N
35
36
AC current CT
Supply
1
2
-
+
NOTE
Wiring diagrams are examples. Use the application's wiring diagram during installation.
Genset and mains contactor latching relays should be compiled against 4 kV surge as per IEC-61000-4-5 standard.
Relay cards used with the controller should be protected against reverse battery voltages.
Analogue input 2 used for Fuel level sensor can be wired with the reference to Battery Negative, see Specifications,
Analogue resistive sensor inputs.
Communication ports for CAN ( terminals 13 and 14) and RS-485 (terminals 31 and 32) have built-in 120 Ω resistors.
If a digital output is connected to a relay, the relay must include freewheeling diodes.
USER MANUAL 4189341226A UK
P2
s2
P1
P2
s1
s2
P1
P2
s1
s2
37
38
39 40
27 28 29 30
AC voltage
genset
Outputs
3
4
5
6
8
9
7
F1
+
B+
G
+
D+
GB
F4
10 11 12 21 22
Digital inputs
(configurable)
CAN A
Analogue inputs
ECU
23 24
25 26
41
42
13 14
Engine
body
L1
L2
L3
N
MB
F5
31 32 33 34
AC voltage
Mains
E-Gov
RS485
17 18 19 20
31 32
GOV
Page 19 of 72