Deif SGC 120 User Manual page 17

Single genset controller
Hide thumbs Also See for SGC 120:
Table of Contents

Advertisement

Terminal
Text
17
GOV_ACT–OUT1
18
GOV_ACT–OUT4
19
GOV_ACT–OUT2
20
GOV_ACT–OUT3
21
DIG_IN D
22
DIG_IN E
ANLG_I_IN (SGC 120)
23
ANLG_IN (SGC 121)
24
ANLG_IN ENG_TEMP
25
ANLG_IN FUEL_LEVEL
26
ANLG_IN LOP
27
GEN_V–IN NTRL
28
GEN_V–IN L3
29
GEN_V–IN L2
30
GEN_V–IN L1
31
MAINS_V–IN NTRL
32
MAINS_V–IN L3
33
MAINS_V–IN L2
34
MAINS_V–IN L1
35
GEN_CT–IN L3 1
36
GEN_CT–IN L3 2
37
GEN_CT–IN L2 1
38
GEN_CT–IN L2 2
39
GEN_CT–IN L1 1
40
GEN_CT–IN L1 2
41
SCP
42
MPU–IN
USER MANUAL 4189341226A UK
Description
Output for actuator (SGC 121 only)
Output for actuator (SGC 121 only)
Output for actuator (SGC 121 only)
Output for actuator (SGC 121 only)
Input from switch D
Input from switch E
Analogue input 4 to 20 mA
Analogue input 4 to 20 mA/2.5 ±2 V
Analogue input from Engine temperature sensor
Analogue input from Fuel level sensor
Analogue input from Lube oil pressure sensor
Voltage input from Generator Neutral
Voltage input from Generator phase L3
Voltage input from Generator phase L2
Voltage input from Generator phase L1
Voltage input from Mains Neutral
Voltage input from Mains phase L3
Voltage input from Mains phase L2
Voltage input from Mains phase L1
CT input 1 from Generator phase L3
CT input 2 from Generator phase L3
CT input 1 from Generator phase L2
CT input 2 from Generator phase L2
CT input 1 from Generator phase L1
CT input 2 from Generator phase L1
Sensor common point
MPU Input
Phoenix connector
5447560
5453499
5441252
Page 17 of 72