Register
Parameter
address
Alarm 8
Auxiliary input A
72
Auxiliary input B
Auxiliary input C
Auxiliary input D
Alarm 9
Auxiliary input E
73
Auxiliary input F
Auxiliary input G
Auxiliary input H
Alarm 10
Gen L1 phase low volt
74
Gen L1 phase high volt
Gen L2 phase low volt
Gen L2 phase high volt
Alarm 11
Gen L3 phase low volt
75
Gen L3 phase high volt
DG phase rotation
Mains phase rotation
Alarm 12
Fuel level open circuit
76
V belt broken
Reserved
High oil pressure detected
Table 10.1
*Interpretation of alarm status results
Value of Register
0
1
2
3
4
5
6-14
15
USER MANUAL 4189341226A UK
Interpretation
Alarm disabled
Alarm not active
Warning alarm active
Shutdown alarm active
Electrical trip alarm active
Notification
Reserved
Unimplemented
Unit/
Scale Factor
Interpretation
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Bits/Sign
13/16-16/16
9/16-12/16
5/16-8/16
1/16-4/16
13/16-16/16
9/16-12/16
5/16-8/16
1/16-4/16
13/16-16/16
9/16-12/16
5/16-8/16
1/16-4/16
13/16-16/16
9/16-12/16
5/16-8/16
1/16-4/16
13/16-16/16
9/16-12/16
5/16-8/16
1/16-4/16
Page 52 of 72