Level 2
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(FLS) Low Fuel Level Shutdown
(SHUTDOWN)
(FLS) Shutdown Threshold
(SHUTDOWN THRESHOLD)
(FLS) Low Fuel Level Notification
(NOTIFICATION)
(FLS) Notification Threshold
(NOTIFICATION THRESHOLD)
(FLS) Fuel Tank Capacity
(FUEL TANK SIZE)
(FLS) Fuel Theft Warning
(FUEL THEFT ALARM)
(FLS) Fuel Theft Alarm Threshold
(FUEL LVL THRESH)
(FLS) Circuit Fault Action
(OPEN CKT ALARM)
(FLS) Fuel Sensor Reference
(FUEL LVL REF)
(FLS) Fuel Level Sensor Calibration Table
Table 6.9
Analogue Input 3 (LOP / DIG F)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
USER MANUAL 4189341226A UK
Range
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 60 s
Enable
Disable
0 to 78 %
Enable
Disable
2 to 80 %
2 to 1000 litre
Enable
Disable
1 to 100 % per hour
None
Notification
Warning
Electrical Trip
Shutdown
Battery Negative
Engine Body
Resistance: 0 to 1000 Ω
Fuel level: 0 to 100 %
Range
Not used
Digital Input F
Lube Oil Pressure
See Digital input source selection in this document
Auxiliary Input F
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Page 26 of 72

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sgc 121

Table of Contents